Miniature, Delay On Make Timers, TBC Minature Timers, Airotronics


Miniature Delay On Make Timers - TBC Minature Timers

Miniature Delay On Make Timers
TBC Miniature Timers

TBC timers are solid-state output units with digital timing and come in a 15/8" square case.

Ease of installation and hook-up is a primary design benefit. All models with integral time adjustment knob or factory-fixed time require only three connections.



Timing Mode

Application of input voltage to the timer starts the time delay. At the end of the delay period, the load is energized. To reset, remove the input voltage to the timer.

  • Digital timing, solid-state MOSFET output
  • 1 Amp current load handling
  • 10 Amps 100 ms (millisecond) surge handling
  • Wide DC voltage range
  • 1% Repeat accuracy
  • Virtually unlimited time ranges
  • Factory-fixed or variable-timing adjustment
  • Totally encapsulated for protection from harsh environments
  • O-ring sealed exposed controls
  • Single screw mounting through center mounting hole
  • Standard 6.35mm (.250") quick connect blade terminals
  • 100% Operational testing before shipping

Repeat Accuracy:: ±0.1%under fixed conditions

Time Ranges: 0.1 sec. to 24 hours (1 sec., 10 sec., 100 sec., and 1000 secs. are standard) Special time ranges available on request.

Reset/Recycle Time: 100 milliseconds

Tolerances: Fixed: ±10% of normal time (optional: -±5%,±1%) Variable: -0%, +15%
Limit:-10% at minimum time

Recycle Effect: None

Temperature Ranges:

  • Storage: -40°C to +85°C
  • Operating: -25°C to +85°C
Life Expectancy: No predictable failure if used within operating parameters
  • Polarity Protection: All DC units have reverse polarity protection
  • Transient Protection: 18 joules
  • Dielectric Strength: 1800V RMS 60 Hz

Power Requirement: .25 watts max.

Weight: 3 oz. (85g) maximum

Solid-State Output: SPST (N.O.)

Load Current: 1 amp continuus, 10 amps 100 ms surge

Time Cycle Interrupt: Resets timer to original state (input Voltage Break)

Mode of Operation Series Input Voltage Time Ranges Time Adjustment Method
Delay On Make TBC 4 8-40 VDC

VARIABLE TIME PERIODS A Variable, integral, knob on timer.

C Fixed, internal, factory set
0001 .1 to 1 sec.
0001 .5 to 1 sec.
0010 .1 to 10 sec.
0100 1 to 100 sec.
1000 10 to 1000 sec.
Any range up to 24 hours avaialble on special order
Specify time in seconds(S) or hours(H)
Examples: 400S is 400 secs
05H5 is 5.5 hours