Cube Relay Repeat Cycle, OFF/ON, Timers, TGKAD Timers, Airotronics,


Cube Relay Repeat Cycle OFF/ON Timers - TGKAD Timers

Cube Relay Repeat Cycle OFF/ON Timers - TGKAD Timers
TGKAD Timers

TGKAD series Cube Relay Repeat-Cycle (Dual Adjustable) On/Off timers are a unique combination of solid-state timing circuitry with a relay output in a compact cube configuration. The time delay for both the “On” cycle and the “Off” cycle can be individually adjusted. These solid-state timers offer the many advantages of a relay output and provide the same functional performance as plug-in relay timers, but at a significant cost savings.


Timing Mode

Application of input voltage to the timer starts the “On” time delay, and energizes the relay. At the end of the “On” time delay, the relay is de-energized, and the “Off” time delay starts. At the end of the “Off” time delay, the load is again energized, the timer returns to the “On” time delay, and the cycling continues as long as input voltage is applied. Removal of the input voltage resets the timer.

  • High current carrying capacity up to 10 amps
  • 100% Load isolation
  • No leakage in N.O. position
  • No heat sinking required
  • Available in any time delay periods required
  • Digital CMOS timing
  • Transient protected
  • No minimum load required
  • Totally encapsulated for protection from harsh environments
  • 100% Operational testing before shipping


Input Voltage:

  • VDC: 12, 24, or 48
  • VAC: 24, 48, 120, or 230, 50/60 Hz

Time Delay:

  • Timing Mode: Repeat-Cycle On/Off
  • Type: Digital CMOS
  • Available Time Range: 0.2 seconds to 24 hours
  • Time Adjustment:
    • variable, with adjustments on timer, or terminals for external resistors or potentiometers

Repeatability: 0.5%

Setting Accuracy:

  • Fixed time period: 10% of nominal time,
  • Variable time range:
  • +15% -5% max. time, -10% min. time

Reset/Recycle Time: 250 milliseconds

Initiate Time: 6 milliseconds or less

Life Expectancy:

  • Mechanical: 20 million operations

  • Electrical: 100,000 operations at maximum load
  • Contact Material: Silver nickel, gold plated, or silver cadmium oxide

Relay Output:

    • SPDT
    • Standard – 6 amps (resistive)
    • Optional – 10 amps (resistive)


  • Polarity Protection: All DC units have reverse polarity protection
  • Transient Protection: 18 joules
  • Dielectric Strength: 1800V RMS 60 Hz

Temperature Ranges:

  • Storage: -40° C to +85° C
  • Operating: -40° C to +85° C

Physical Data:

  • Mounting: Surface with one #8 screw
  • Connection & Termination: 0.25" quick connects
Mode of Operation Series Input Voltage Time Ranges Time Adjustment Method Relay Output Form Options
Repeat-Cycle On/Off TGKAD
  1. 120 VAC
  2. 230 VAC
  3. 24 VAC
  4. 24-28 VDC
  5. 48 VAC
  6. 48 VDC
  7. 12 VDC
  8. Any in between AC voltage (specify)
  9. Any in between DC voltage (specify)

0001 .05 to 1 sec.
0010 .1 to 10 sec.
0100 1 to 100 sec.
1000 10 to 1000 sec.

Any range up to 24 hours available on special order.

Specify time in full seconds or hours followed by the letter “S” or “H” and the decimal amount of the main time unit.
  • 5S5 is 5.5 seconds
  • 5H5 is 5.5 hours
  1. Variable, integral, knob on timer.
  2. Variable, external, knob remote.
  3. Fixed, internal, factory set.
  4. Fixed, external resistor remote.
  1. SPDT
  2. SPST (N.O.)
  3. SPST (N.C.)
  1. Heavy Duty,10 amps (6 amps relay standard)
  1. 20 amps (1.5 HP)

Site Design: Process Controls And Instrumentation