True-Off Delay Timer With IC Digital Circuits - TQMT Timers
True-Off Delay Timer With IC Digital Circuits - TQMT Timers
|
|
 |
TQMT Timers
The TQMT is a True Off Delay Timer with IC digital circuits and an optional instantaneous contact. It comes in a magnal round base for plug-in installation and handles current up to 10 amps with fixed or adjustable time periods.
Download
|
Timing Mode
Apply input power for a minimum of
100 milli-seconds to assure time out. Instantaneous contact and timed contacts
transfer. Remove input power, instantaneous contact drops out, timed contacts
remain closed for duration of selected time (off-delay) then drop out. Reapply
power for new cycle.
|
 |
|
FEATURES |
-
CMOS IC digital timing
-
Timing contacts and instantaneous contacts in same timer
-
Relays are sealed
-
Proven circuitry
-
Magnal (11 pin) plug-ins
- Fixed or variable time adjustment
|
-
Timing ranges from .1 to 300 seconds
standard (special time settings and
ranges also available)
-
0.1% Repeat accuracy
- 100% Operational testing before shipping
|
| BASIC WIRING AND DIMENSIONS |
 |
| SPECIFICATIONS |
|
Input Voltages: VAC: 120, 230, 50/60 Hz
Operating Voltage: 20% of nameplate voltage
Relay Contact Ratings: 10 amps DPDT
Repeat Accuracy: 0.1% under fixed operating
conditions
Reset Time: 100 milliseconds
Tolerances:
- Fixed: 10%, Optional: 5%, 1%
- Variable: +20%, -0, Optional: +10%, -0%
Note:Tolerances on variable units are with respect to upper limit only. Timers with time periods greater than 10 sec. will have a 100 to 1 ratio, i.e., 1 to 100 seconds. Timers with the time periods less than 10 sec., will have a 10 to 1 ratio, i.e., .99 to 9.9 seconds, .5 to 5 seconds.
|
Life Expectancy:
- Mechanical: 1 million operations
- Electrical: Up to 100,000 operations at full
current load
Protection: Transient Protection: 25 joules
Temperature Ranges:
- Storage: -40° C to +85° C
- Operating: -25° C to +85° C
Housing Material: High impact, UL approved
black Lexan
|
| SELECTION PROCEDURE
|
| Mode of Operation |
Series |
Input Voltage |
Time Ranges |
Tolerance |
Time Adjustment Method |
Base Style |
Options |
True Off Delay
(Instantaneous Contact) |
TQMTIC |
- 120 VAC
- 230 VAC
|
VARIABLE TIME PERIODS |
X
Standard
(Fixed: 10%
Variable: +20%
-0%)
E
F
G
Optional
(Adjust.: +10%,
-0%)
|
| A |
Variable, integral, knob on timer.
|
| C |
Factory-Fixed time |
|
2
|
H
|
0010 .1 to 10 sec.
0100 1 to 100 sec.
0300 5 to 300 sec.
|
| FIXED TIME PERIODS |
Specify time in full seconds or hours followed by the letter "S" or "H" and the decimal amount of the main time unit.
Examples: 5S5 is 5.5 secs
5H5 is 5.5 hours |
|