Process Controls Home
 
 

Indoor Air Quality Data Logger ACR IAQ

IAQ - Indoor Air Quality
The Indoor Air Quality logger combined with Telair 7001 monitor can record the three leading air indicators which are temperature, RH, and CO2.


temperature, RH, Carbon Dioxide
IAQ - Indoor Air Quality 

Battery

3.6 volt Lithium, guaranteed for 10 years

Logger Resolution

8 bits (1 part in 256)

Number of Channels

  • one intrenal temperature sensor
  • one internal RH sensor
  • one for CO2 sensor
  • two for optional remote temp & RH sensor

Temperature Sensor Specification

  • NTC Thermistor; -40 to 70 °C (-40 to 158 °F)
  • accrracy: ±0.2 °C from 0 to 70 °C; ±0.5 °C from -40 to 0 °C (±0.36 °F from 32 to 158 °F; ±0.9 °F from 32 to -40 °F)

RH Sensor Specification

  • capacitive thin polymer film
  • ±4% from 10 to 90% (-20 to 40 °C [-4 to 104 °F])
  • better than 0.04% between 25 and 60% RH at 25 °C (77 °F)

CO2 Sensor Specification

  • response time: <60 seconds
  • accuracy: ±50 ppm or ±5% of reading, whichever is greater
  • warm up time: <60 seconds at 22 °C

PDF

Indoor,Air,Quality,Data,Logger,ACR,IAQ

Size 107 mm x 74 mm x 22 mm (4.2" x 2.9" x 0.9")
Weight: 110 grams (3.75 ounces)
Case Material: NorylŪ Plastic
Operating Limits: -40°C to 70°C (-40°F to 158°F) and 0 to 95% Relative Humidity (non-condensing)
Clock Accuracy: +/-2 seconds per day
Battery: 3.6 volt Lithium, 1 Amp-Hour
Power Consumption: 5 to 10 microamps (continuous)
Battery Life: 10-years warrantied (under normal use) Factory replaceable
Mounting: Magnetic backing or locking eyelet
Memory Size: 32 K (32,768 readings)
Sampling Method: 1. Continuous (First-in, First-out) 2. Stop when full (Fill-then-stop)
Sampling Rate: User selectable rates between 8 seconds to once every 5 days
Resolution: 8 bits (1 part in 256)
External Connector: Removable screw-type terminal strip with Common (-) connection
PC Requirements: IBM PC or 100% compatible running MSŪ Windows 3.1, '95, '98, or NT, with at least 2 MB RAM, 2 MB of hard drive disk space and one free serial port
Product Approvals: Meets Part 15 for Digital Devices of the Code of Federal Regulations of the Federal Communications Commision (FCC). Meets Class A radiated and conducted emission requirements of Section 2 of the Radio Interference Regulations of Communications Canada. IEC801-2, 3, 4 and EN55011 covering ESD, RFI Immunity, EFT/Burst and Radiated Emissions respectively, for the Commission of the European Communities (CE)
Resistance to X-Rays: Tested for protection against a 160kV dose @ 5mA for 30 seconds (150mA-sec) @ 38 inches F.F.D. (about 100 times that of an airport X-Ray machine). Tested for protection against Gamma Ray (equivalent to 0.137 - 1.38 mega volts) IR 192 - 28 curies @ 30 second exposure source to object distance 5"


Powerful Solutions for Instrumentation & Control Problems!