Roline L series
recommended application range: 0...100%RH and 0...38°C / 32...100°F
accuracy: ± 3%RH and 0.5ºC / 0.9ºF
building automation / energy management systems / industrial HVAC
humidity and / or temperature
2-wire loop powered (4-20 mA) or 3-wire versions
(4-20 mA, 0-5V or other)
NEMA 4 enclosure (except space mount model) |
 |
M1 series
recommended application range: 0...100%RH and
-40...60°C / -40...140°F
accuracy: ± 2%RH and 0.3ºC / 0.5ºF
building automation / energy management systems / industrial HVAC
humidity and / or temperature
2-wire loop powered (4-20 mA) or 3-wire versions
(4-20 mA, 0-5V or other)
NEMA 4 enclosure (except space mount model) |
 |
M2 series
recommended application range: 0...100%RH and
-40...85°C / -40...185°F
accuracy: ± 1.5%RH and 0.3ºC / 0.5ºF
industrial HVAC
Humidity and temperature
Up to 85°C/185°F at probe
± 1.5%RH and 0.3ºC / 0.5ºF accuracy
2-wire loop powered or 3-wire versions
NEMA 4 enclosure
Plug-in HygroClip® probe facilitates field maintenance |
 |
FST series
recommended application range: 35...50%RH and
20...25°C / 68...78°F
accuracy: ± 1.0%RH and 0.2ºC / 0.4ºF
semi-conductor fab areas / clean rooms and other narrow range HVAC
humidity and temperature
2-wire loop powered (4-20 mA) or 3-wire versions
(4-20 mA, 0-5V or other)
Narrow range output signals for precise measurement |
 |
M3 series
recommended application range: 0...100%RH and
-40...85°C / -40...185°F
accuracy: ± 1.5%RH and 0.3ºC / 0.5ºF
industrial HVAC / energy management systems
Humidity and temperature
Dew point, mixing ratio, enthalpy, etc. also available
± 2%RH and 0.3ºC / 0.5ºF accuracy
Up to 85°C/185°F at probe
Analog output signals and networkable digital output
NEMA 4 enclosure
Plug-in HygroClip® probe facilitates field maintenance |
 |
HygroFlex series
recommended application range: 0...100%RH and
-50...200°C / -58...392°F
accuracy: ± 1.5%RH and 0.3ºC / 0.5ºF
industrial process control
Humidity and temperature
Dew point, mixing ratio, enthalpy, etc. also available
Wide range of probes to satisfy every application
User configurable
Analog output signals
Digital output
Networkable
NEMA 4 enclosure |