Process Controls Home
 
 

Roline L Series: Humidity Temperature Transmitter

Specifications | Diagrams | Field Service | Accessories


Roline L Series Humidity Temperature Transmitter is designed for HVAC applications that require low maintenance, stable sensors at a moderate price.

Roline,L,Series,Humidity,Temperature,Transmitter

  • Well proven Rotronic Hygromer humidity sensor
  • Measuring range 0...100 %RH and 0...50°C or 0...100°F
  • ± 3.0% RH / ± 0.5°C (± 0.9°F) accuracy
  • Long term stability of better than 1% RH per year
  • Potentiometer free - digital calibration
  • On-site loop validation and calibration with HygroPalm 3 calibrator
  • Duct, wall and space mount configurations
  • 2-wire loop-powered or 3-wire versions
  • Available as RH & temperature, RH only or temperature only transmitter
PROBE
L12
L13
Humidity sensor Rotronic Hygromer ™ C94 thin film capacitive
Temperature sensor Pt100 RTD
Operating limits 0...100%RH
-40...60°C / -40...140°F
Repeatability better than 0.5%RH and 0.1°C/°F
Humidity sensor stability better than 1% RH per year
Sensor protection wall and duct models: PVC foam filter
 space mount models: n/a
Probe material wall and duct models: Polycarbonate
space mount models: n/a
TRANSMITTER
L12
L13
Circuit type 2-wire loop-powered 3-wire
Signal type 4...20 mA 0...20 mA, 4...20 mA
0...1V, 0...5V, 0...10V
Measuring range 0...100% RH
0...50°C or 0...100°F
Accuracy at 23°C ± 3.0% RH / ± 0.5°C (± 0.9°F)
Operating limits 0...99% RH non condensing
-40...60°C (-40...140°F)
Power supply 18...28 VDC, 18 + 0.02 x load
2 x 20 mA
18...35 VDC (50 mA) or 12...24 VAC
Maximum load for current outputs 250 Ohm
Minimum load for voltage outputs n/a 1000 Ohm
Electrical connections wall and duct models: cable grip and terminals
space mount model: terminals
Housing material ABS
Protection grade wall and duct models: IP65/NEMA4
space mount model: IP52 / NEMA5
Weight 200 g / 4.2 oz

L13    3-wire
Current outputs Voltage outputs
L12    2-wire loop-powered

Note: 1 and 3 (+) are connected



Service cable ACRLXB5

 

Each Roline L series transmitter features a service connector that can be accessed without disturbing the output signals.

Service cableACRLXB5 is used to connect the service connector of the transmitter to probe input 2 of the HygroPalm 3 portable indicator.

Field Calibration

Using the HygroPalm 3 indicator and the ACRLXB5 service cable, the following can be done:

a) 1-point adjustment of the transmitter against a reference probe connected to the HygroPalm

b) single- or multi-point adjustment against a reference environment (requires a humidity generator). When no humidity generator is available, ROTRONIC offers easy-to-use certified humidity standards to generate known humidity values. See below for details.

Validation of the signal loop

By displaying the signals of the transmitter with the HygroPalm 3, the entire measuring loop can be validated: probe, transmitter, wiring and central processing unit.

Calibration standards Certified Humidity Standards: if you do not have access to a humidity generator, the Rotronic humidity standards offer a reliable and convenient way to generate a reference humidity condition during probe calibration. The Rotronic standards are shipped with an internationally accepted certificate, meeting in full the requirements of quality systems such as ISO 9000. The standards are available in boxes of 5 glass ampoules of the same value, and can be stored indefinitely. Standards in the range of 5 to 95 %RH are non-saturated aqueous salt solutions. The 0 %RH humidity standard is made of small granules of a highly porous ceramic. A Material Safety Data Sheet is available for each standard.
Calibration devices ER-15 calibration device: this is a small airtight container that fits on the probe and seals around the humidity sensor. During calibration, a known reference humidity is produced inside the calibration device by means of a humidity standard.
Accessories
HygroPalm 3          HygroPalm 3,  field calibrator
ACRLXB5 Cable: service connector Roline L  to HygroPalm 3 for field calibration and loop validation.

ER-15 Calibration device
EAXX-SCS Certified humidity standards (5 per box)
XX = 00. 05, 10, 20, 35, 50, 65, 80, 95%RH


Powerful Solutions for Instrumentation & Control Problems!
Roline L Series: Humidity Temperature Transmitter

Site Designed By Panther Marketing