Process Controls Home
 
 

Setra Very Low Differential Pressure Transducers
Setra Model 265

At ±1.0% Full Scale accuracy (±0.4%, ±0.25% FS optional), Setra's Model 265 provides superior positive and negative pressure sensing required for high efficiency, air-control systems. An optional snap-on conduit enclosure, molded from high impact Lexan®, is avaialble.

Setra,Very,Low,Differential,Pressure,Transducers

Applications

  • HVAC Equipment
  • Energy Management
  • Variable Air Volume (VAV)
  • Environmental Pollution Control
  • Static Duct & Clean Room Pressures
  • Oven Pressurization & Furnace Draft Controls
  • Medical Instrumentation
Model 265 Specifications
Electrical Output Voltage

0 to 5 VDC

Bidirectional Output (Voltage) at Zero 2.5 VDC
Electrical Output Current

4 to 20 mA

Accuracy
(RSS Method)

±1.0% FS
(Optional Accuracies: ±0.4%, ±0.25%)

Type of Pressure Very Low Differential Pressure
Pressure Ranges Unidirectional:
0 to 0.25, 0.5, 1.0, 2.5, 5.0, 10, 25, 50, 100 in.WC
Bidirectional:
0 to ±0.1, ±0.25, ±0.5, ±1.0, ±2.5, ±5.0, ±10, ±25, ±50 in.WC
Thermal Effects
Thermal Compensation °F (°C):
0 to +150 (-18 to +65)
Zero/Span Shift %FS/°F (°C):
0.033 (0.06)
Media Typically air or similar non-conducting gases

 

* Specifications subject to change without notice.