Anti-Short Cycle Timer - Solid State Cube Relay Timer - TH3AC Timers
Solid State Cube Relay Timer
|
|
 |
TH3AC Timers
The TH3AC timers are an anti-short cycle timer with solid-state output for compressor protection. An optional "delay on make" function is offered for sequencing or prevention of contactor chatter. A simple 3 terminal connection and encapsulated 2" x 2" package.
|
Timing Mode
When power is applied (thermostat closes) the load energizes. When power is removed the "lockout" time delay begins, preventing the load from turning on until the end of the delay. An optional "delay on make" is available, delaying the initial load output for up to 5 minutes. |
 |
|
FEATURES |
- 1 Amp current load
- 10 Amps single AC cycle surge handling
- 3 Operating voltages 24/120/230VAC
- Factory fixed or potentiometer adjustable
- Totally encapsulated for protection from harsh environments
- Optional delay on make
|
- 24 VAC unit has anticipator resistor-bypass circuit
- Single screw mounting through center hole
- Industry standard three terminal (.250") quick connects
- 100% Operational testing before shipping
|
| BASIC WIRING AND DIMENSIONS |
 |
| SPECIFICATIONS |
Input Voltage:
- VAC: 24 (±20%)
- VAC: 120/230, 50/60 Hz
Anticipator Resistor:
- (24 VAC only)
- 2000 ohms minimum
Time Delay: Up to 10 minutes Lockout Time: Factory fixed or variable with knob on timer
Tolerance: +35%-15% of nominal time Initiate Time: 16 milliseconds
|
Life Expectancy:
- No predictable failure if used within operating parameters
Protection:
- Transient Protection: 18 joules
- Dielectric Strength: 1800 RMS 60 Hz
Temperature Ranges:
- Storage: -40°C to + 85°C
- Operating: -40°C to +70°C
- Humidity: 95% relative
Physical Data: Surface mount with single #8 or #10 screw Connection & Termination: 0.25" quick connects
|
| SELECTION PROCEDURE |
| Mode of Operation |
Series |
Input Voltage |
Time Ranges |
Time Adjustment Method |
Options |
Anti-Short Cycle (Lockout) |
TH3AC |
- 120 VAC
50/60 Hz - 230 VAC
50/50 Hz - 24 VAC
50/60 Hz |
VARIABLE TIME PERIODS |
- Integral knob
C Factory fixed |
SXXX On delay (up to 5 min.) XXX Time Period XXS Time in sec. Example: 30S = 30 second fixed time |
060 - 1 min. 0120 - 2 min. 0180 - 3 min. 0240 - 4 min. 0300 - 5 min. 0600 - 10 min. XXX - fixed |
| FIXED TIME PERIODS |
| Any fixed time up to 10 minutes |
|
|