The LCU032 Series Temperature/Process Indicators set a new standard in power, flexibility, and value in a low cost 1/32 DIN control. While the LCU032 is primarily a control, it is equally useful as an indicator. The same flexibility of inputs combined with the large single display, makes the LCU032 an excellent choice for most any application requiring indication. As an additional bonus, the output usually used for the set point can be programmed as a 4 to 20 mA retransmission output. Where else can you get an indicator with a large display, universal input, retransmission, and alarm for a price that competes with many single use, display only indicators?
The LCU032 offers universal input (13 thermocouple scales, 2 RTD types, voltage, and current).
Optional for the LCU032 is RS-485 Modbus Serial Communication.
INPUT RANGES
| Model Number |
Range °F |
Range °C |
| Type J Thermocouple |
-300 to +2300 |
-199.9 to +999.9 |
| Type K Thermocouple |
-300 to +2500 |
-200 to +1370 |
| Type K Thermocouple |
0 to 2300 |
-199.9 to +999.9 |
| Type T Thermocouple |
-300 to +750 |
-199.9 to +400 |
| Type E Thermocouple |
-300 to +1800 |
-199.9 to +999.9 |
| Type L Thermocouple |
-300 to +1300 |
-199.9 to +900.0 |
| Type R Thermocouple |
32 to 3100 |
0 to +1700 |
| Type S Thermocouple |
32 to 3100 |
0 to +1700 |
| Type B Thermocouple |
+32 to +3300 |
0 to +1800 |
| Type N Thermocouple |
-300 to +2400 |
-200 to +1300 |
| Type U Thermocouple |
-300 to 750 |
-199.9 to +400 |
| Type W Thermocouple |
32 to 4200 |
0 to 2300 |
| Platinel II |
32 to 2500 |
0 to 1390 |
| 100 Ohm Plt. 0.00385 DIN RTD |
-328 to 1607 |
-200 to +875 |
| 100 Ohm Plt. 0.00392 NIST RTD |
-328 to 1607 |
-200 to +875 |
| 1 to 5 V* |
Sscalable Units from -1999 to +9999 |
PHYSICAL DATA
Selectable Inputs: (See range chart) 13 Thermocouple, 2 RTD, DC Voltage, or DC Current selectable.
Input Characteristics:
Thermocouple = 1 megohm minimum.
Current = 250 ohms (shunt resistor).
RTD current = 500µA (Max. lead resistance = 10 ohms/wire).
Voltage = 1 megohm.
Sample Time: 250mS.
Sensor Break Protection: Upscale or downscale for thermocouples, upscale only for RTD.
Set Point Range: Selectable (See Range Chart).
Display: One 4 digit, 7 segment LED.
Alarm On-Off Differential: Adjustable 0.0 to 100% of full scale.
Accuracy: ±0.5% of span, ±1 least significant digit.
Resolution: 1 count or 1 degree or 0.1 degree per range.
Temperature Stability: 100 ppm/°C typical, 200 ppm/°C max.
Reference Junction Accuracy: ±1.5°C @ 15 to 35°C, ±2.0°C @ 0 to 50°C.
Supply Voltage: 100 to 240 VAC 50/60 Hz.
Power Consumption: 10 VA maximum.
Operating Temperature: 0 to 50 °C (+32 to 131 °F).
Storage Temperature: -25 to +70 °C (-40 to 176 °F).
Humidity Conditions: 20 to 90% non-condensing.
Memory Backup: Nonvolatile memory. No bateries required.
Output Ratings:
Relay: SPST, 1 A @ 240 VAC resistive.
Current (non-isolated): 4 to 20 mA across 600 ohms max.
Panel Cutout: 454 mm x 22 mm (1.775" x 0.874").
Depth Behind Mounting Surface: 100 mm (3.94").
Weight: 114 g (4 oz).
Agency Approvals: CE, UL E83725.
Front Panel Rating: IP65 (Type 4X).
Communications Option:
Standard: RS-485.
Address Range: 1 to 99.
Connection: 2-wire, Half Duplex
Communications Rate: Selectable, 600, 1200, 2400, 4800, 9600 Baud.
Start Bit: 1.
Data Bits: 7 or 8, programmable.