Description
Double setpoint controller size 48x48mm with frontal extraction.
Universal analog input for thermocouples J, K, S, R, PT100, PTC 1K, NI100, linear signals 0...10V, 0...20mA, 4...20mA e 0…40mV (for load cells). Double display (green and red), 4 Digits (9999).
Two configurable outputs: one change-over relay (8A resistive), one relay 5A configurable as alarm (deviation, band, general) or one output for SSR command/alarm or 4...20mA (command or retransmission of Setpoint/Process). One digital input is available for switch of setpoint (setpoint1-setpoint2) or Hold function (usefull with Infrared Sensor) Memory card allows easy and quick configuration and start-up.
The unit may also be configured by parameter as Programmer for simple firing cycles.
Function Open/Close with Open loop for motorised valves also available, as well as the possibility to control manually the percentage of output power.
|
|
|
Ideal Application
Injection moulding
Laboratory ovens
Load cells
Water control
Valves control
Packaging
Safety unit
Pressure control
Food industry
Woodworking machinery
|
Technical
data
SIZE: 48x48(frontal)x112(depht)mm
SUPPLY: 24Vac, 12...24Vac/Vdc, 115/230Vac
POWER CONSUMPTION : 3W
DISPLAY: dual display 4 digits, red LEDs, decimal point
OPERATING CONDITIONS: 0-45°C, 35..95rH%
INPUTS: 1 configurable for
TC J, K, S, R, PT100, NI100, 0...10V,0/4...20mA, o…40mV.
OUTPUTS:
1 change-over relay 8A resistive
1 relay 5A resistive, configurable also as SSR 12V-30mA /4...20mA(command or retransmission)
CONTROL MODES: ON/OFF, P, PI, PID-Autotuning
ACCURACY: 0.5%±1digit for Tc/RTD; 0.2%±1digit for V/mA
SAMPLING TIME: 66ms
SEALING: IP54 Frontal, IP30 Box, IP20 Terminal blocks
CONFIGURATION: parameters protected by password
Memory card for quick configuration and programming.
|