pH,cooling,tower,controller,microprocessor,based,model,2350,lakewood,instruments

Microprocessor Based pH Cooling Tower Controller Model 2350



Microprocessor Based pH Cooling Tower Controller Model 2350

 
Model 2350 Microprocessor-Based pH Cooling Tower Controllers

Product Information

LONWORKS® Technology is the latest in microprocessor capability that gives the user the highest level of application flexibility. A large graphic screen, multiple inputs and very easy setup with easy field upgrade characterize this new technology.

Features
  • Differential pH sensor with diagnostics indicate fouled reference or broken glass.
  • Integral flowsight & flowswitch lockout.
  • Records both makeup (MTR1) and blowdown (MTR2) water meter total gallons.
  • Configure blowdown water meter (MTR2) as second makeup meter.
  • Four user-selectable relay options (four additional with NRLY):
    • Feed by setpoint, direct or reverse;
    • Water meter actuated feed. MTR1, MTR2 or sum;
    • Feed by percentage of time;
    • Schedule feed timer (-RTC Option);
    • General alarm contact.
  • Three security levels:
    • View only
    • Operator
    • Technician
  • Four different languages.
    • English Spanish (standard)
    • English French (optional)
    • English German (optional)
Benefits
  • Multiple control options in a single economical package.
  • Very accurate control of chemical feed.
  • Very low maintenance.
  • Tolerant to power surges and brownouts.
  • Power cord, plug outlets and attached plumbing make installation easy. There is plenty of protected room inside the enclosure for electrician wiring.
  • Very accurate monitoring of the evaporated water.
  • Has expansion slots to add additional control, such as chiller loop monitor.
Specifications
Inputs
Power 80-300 VAC
Sensor pH combination glass electrode
Temperature comp. Automatic
Flow switch Dry contact
Water Meter Input Two contacting head or open collector
Outputs
Relays Four, 3 Amps @ 120 VAC
4-20 mA Two, isolated w/-35L
Sensor/Plumbing
Pressure 140 psi (9.7 bar) @ 100°F (38° C)
Max. Temperature 140°F (60° C)
Min. Flow 1 gpm (3.8 Lpm)
Controller
pH Range 0-14 pH
pH Accuracy ±0.05 pH
pH Resolution 0.01 pH
Deadband Adjustable
Setpoints Direct or Reverse (configurable in the field)
Feed timer Adjustable
Keypad Numeric
Display Illuminated 128x64 pixel LCD
Ambient Temperature 32-158° F (0-70° C)
Enclosure ABS Plastic
NEMA 4X Optional

Ordering Information
2350   LONWORKS Technology-based pH controller with 4 selectable relays for HIGH/LOW setpoints or alarms. Includes plumbing, sensor, flowswitch, power cord and outlets. pH range is 0-14 pH with adjustable deadband.
CONTROLLER OPTIONS (optional, select no more than three)
-RTC   Adds 24-hour clock and calendar to controller (required to configure relays to feed chemicals/biocides based on time of day and for data acquisition if using the -RS2L Option). NOTE: Adding an -RTC card does NOT add relays.
-35L   Two 4-20 mA outputs configurable for remote data acquisition of pH.
-RS2L   Communications node with shareware software; requires -RTC Option.
-NIN ;   Network interface node allows 1 NRLY and/or up to 3 NCON/NCKTs to be added.
ENCLOSURE OPTIONS (optional)
-WP   Weatherproof and watertight. ½ inch knockouts. No outlets or power cords.
LANGUAGE OPTIONS (optional, choose one, English and Spanish Standard)
-EF   English and French.
-EG   English and German.
REMOTE NODE OPTIONS (optional; MUST purchase -NIN Option above)
NRLY   Four additional relays with enclosure (1 per 2000 Series Controller).
SOFTWARE AND EXTERNAL MODEMS
LRWS   Windows-based software for computer to communicate with 2000 Series Controllers.
MD4X   High-Baud modem in NEMA 4X enclosure ready to power.
MD   High-Baud modem for use with 2000 Series Controllers.

 


Site Designed And Maintained By Panther Marketing & Design