Product Specification
|
Description |
| Conductivity Range |
0.00 to 19.00 mΩ/cm
0.000 to 1.999 mΩ/cm |
0.01 mΩ/cm
0.001 mΩ/cm |
| Accuracy |
±1 % full scale |
| Temperature Range |
-9.9 to 125 °C |
Resolution &
Relative Accuracy |
0.1 °C &
±0.5 °C |
| Temperature Sensor |
Pt 100/ Pt 1000 (jumper selectable) |
| Temperature Compensation |
Auto / Manual (reference at 25 °C) |
| Set Point and Controller Functions |
| Function |
Limit / Proportional (pulse or frequency) controller |
| Switching Hysteresis |
0 to 10% full scale |
| Pickup / Dropout Delay |
0 to 2000 seconds |
Contact Outputs, Controller
|
2 potential free change-over contacts |
| Switching Voltage / Current / Power |
Max 250 VAC / Max 3A / Max 600VA |
| Alarm Functions
|
| Function (Switchable) |
Launching or Pulse |
| Pickup Delay |
0 to 2000 seconds |
| Switching Voltage / Current / Power |
Max 250 VAC / Max 3A / Max 600VA |
| Electrical Data and Connections |
| Power requirement |
110/ 220 VAC (jumper selection) |
| Frequency |
48 to 62Hz |
| Signal Output |
0/4 to 20mA, galvanically isolated |
| Load |
Max. 600 Ω |
| Connection Terminal |
Terminal blocks 5-pole/ 17-pole, removable |
| Main Fuse/ Fine Wire Fuse |
Slow-blow 250 V/ 100 mA |
| EMC Specifications
|
|
Emitted Interference
|
According to EN 50081-1
|
| Immunity to Interference |
According to EN 50082-1 |
| Environmental Conditions
|
| Maximum Relative Humidity |
10 to 95%, non-condensing |
| Ambient Temp. Operating Range |
0 to 50 °C |
| Mechanical Specifications
|
| Dimensions |
175 x 96 x 96 mm |
| Weights |
Max. 0.7kg |
| Material |
ABS with polycarbonate |
| Insulation |
IP 54/ IP 65 |