Loop Alarms Process/Alarm Switches accept inputs from thermocouples (1290), RTDs (1490). SPDT relay outputs can be set for latching or non-latching, direct or reverse action and high or low function. Output behavior is easily programmable via switches. Mount in standard 11-pin sockets.
SPECIFICATIONS
Isolation: 1500 Volts RMS between input, outputs and power.
Power Supply: 85-265 VDC/VAC, 50-400 Hz.
Setpoints: Adjustable from 0-100% of span.
Deadband: Adjustable from 0.25-100% of span.
Drift: ±0.02% /°C typical, ±0.05% /°C maximum.
Ambient Operating Temperature: 32 to 131°F (0 to 55°C) non-condensing.
Input Impedance: (1290) 3 megohms, Current input=10 ohms.
Search Current (1490): Cu 10 = 5 mA. Plt 100 , Ni100 , Ni120 ; = 500µA. Plt 500 ;, NiFe 1000 , NiFe 2000 = 100 µA. Plt 1000 ; = 50µA.
Relay Output: SPDT, one set per setpoint, 5A @ 250 VAC resistive.
Latch Circuit Reset: Automatic at power up. Manual with reset switch.
Lead Compensation Error (1490): 0.02%/ .
Indicators: One dual color LED per setpoint; red = On, green = Off.
Open Thermocouple Protection (1290): Selectable upscale or down-scale.
Dimensions: Including socket pins, 2-3/8" W x 3-7/16" H x 1-3/4" D (60.3 W x 87.3 H x 44.4 D mm).
|
Model 1290 Input Type and Ranges
|
Type E Thermocouple -454 to +302°F (-270 to +150°C) -454 to +554°F (-270 to +290°C) 32 to +302°F (0 to +150°C) 32 to +554°F (0 to +290°C) 32 to +1220°F (0 to +660°C) 32 to +1832°F (0 to +1000°C)
Type S Thermocouple 32 to 1922°F (0 to +1050°C) 32 to 3200°F (0 to +1760°C)
Type T Thermocouple -454 to +410°F (-270 to +210°C) -454 to +734°F (-270 to +390°C) 32 to 410°F (0 to 210°C) 32 to 734°F (0 to 390°C)
|
Type J Thermocouple -346 to +374°F (-210 to 190°C) -346 to +680°F (-210 to 360°C) 32 to +374°F (0 to190°C) 32 to +680°F (0 to 360°C) 32 to +1400°F (0 to 760°C)
Type K Thermocouple -454 to +482°F (-270 to +250°C) -454 to +896°F (-270 to +480°C) 32 to 482°F (0 to 250°C) 32 to 896°F (0 to 480°C) 32 to 2501°F (0 to 1372°C)
Type R Thermocouple 32 to 1778°F (0 to 970°C) 32 to 3200°F (0 to 1760°C)
|
|
Model 1490 Input Type and Ranges
|
Pt 100, 500,1000 RTDs 32 to 212°F (O to 100°C) 32 to 572°F (O to 300°C) 32 to 932°F (O to 500°C)
Ni100 RTDs -58 to +302°F (-50 to +150°C)
|
Ni120 RTDs -58 to +482°F (-50 to +250°C)
Cu10 RTDs 32 to 482°F (0 to 250°C)
NiFe 1000, 2000 RTDs -58 to +392°F (-50 to +200°C)
|
|