| Signal |
Input Impedance |
| 4-20 mA |
200 ohms |
Control Range: 6 to 97% of line voltage.
Linearity: RMS load voltage is linear within 2% of span of the command signal.
Zero and Span Adjustments: User adjustable over range of ±20% of span.
Isolation: Dielectric strength input/line & load voltage/heat sink 400V(RMS). Insulation resistance input/line & load voltage/heat sink 10
10 ohms. Maximum capacitance input to output 8pf.
Cooling: Convection.
Mounting: Must be mounted on vertical surface with fins vertical. Units may be mounted adjacent to each other. Heat sink is electrically isolated.
Line Voltage: 240 or 480 VAC +10%, -20% 50/60 Hz.
Diagnostic Indicator: The intensity of an LED varies as a function of the command signal. Feature provides a quick and safe means to check controller operation.
Weight: 1025: 10 thru 40 amp - 2 lb, 70 amp - 6 lb; 1032: 10 thru 40 amp - 5 lb, 70 amp - 9 lb.
Environment: Operating: 32 to 131°F (0 to 55°C); Storage: -40 to 176°F (-40 to 80°C).
dv/dt & Transient Voltage: 200 volts/µsec minimum. A dv/dt snubber and a metal oxide varistor (MOV) are provided to protect against high frequency transients (dv/dt) and voltage spikes.
Dissipation: 1.5 watt per amp of controlled current.
Recommended Fusing: Special semiconductor fuses are not required. It is recommended that the controller and load be protected with fast acting class "T" fuses such as Bussmann type JJS or JJN fuses.