Made with special limits-of-error material for better accuracy
Standard insulation provided with 304 and 316 SS sheaths, high purity insulation provided with Inconel 600 sheath
Maximum continuous operating temperature for the standard transition is 350ºF (177ºC). A high temperature transition 900ºF (482ºC) maximum can be provided by ordering Special Requirement Option H in Box 11
Standard lead wire termination is 3/4 stripped leads
.063 to .125 O.D. thermocouples use 24 gauge lead wire and .188 to .375 O.D. thermocouples use 20 gauge lead wire
MgO Insulated Thermocouple Assembly Transition to Lead Wire