Frigid-X
Cabinet Cooler Operation
Filtered, compressed air enters
the Frigid-X Cabinet Cooler and through the vortex
tube component. The air is split into into two streams,
one hot and one cold.
The muffled hot air from the vortex tube is expelled through
the top of the air conditioner. The cold air is directed into
the enclosure through the cold air distribution hose. Hot air
inside the enclosure rises and exits to atmosphere via the air
exhaust at a slight positive pressure. The enclosure is both
purged and cooled with clean air. No outside air enters the
enclosure.
Frigid-X™ Cabinet
Cooler Advantages
-
- Compact
- No CFC's
- Fast installation
- Stabilize enclosure temperature
and humidity
- Virtually maintenance free
(No Moving Parts)
- Mounts in a standard electrical
knockout
- Stops heat damage and nuisance
tripping
- Eliminates fans and filters
- Prevents dirt contamination
by keeping enclosure at positive pressure
- Units applicable to all environments
including high temperature to 200ºF
Frigid-X™
Cabinet Cooler Applications
-
- Frequency Drives
- CCTV Cameras
- NC/CNC Systems
- Scanners
Frigid-X™ Cabinet
Cooler Selection
Cabinet
Cooler Air Conditioning Systems Frigid-X comes with a
5 micron filter with an automatic drain for the compressed air
supply to insure clean, dry air and an air distribution kit
to circulate the cold air inside the enclosure for even cooling.
Cabinet Cooler Air Conditioning
Systems Frigid-X
is available with or without thermostat control.
When constant cooling
and a constant positive purge is required we recommend the continuous
operating version without the thermostat and solenoid valve.
The cooling effect can be controlled by adding a regulator in
line to reduce pressure for reduced cooling when it is not required
and to conserve energy.
Systems utilizing a thermostat and solenoid valve saves air
by activating the air conditioner only when the internal temperature
reaches a critical level. The adjustable thermostat is factory
set at 95°F but can be readjusted on site.
Thermostat and solenoid valve systems are recommended where
the heat load can fluctuate (such as for frequency drives) and
where a continual purge is not required. The thermostat and
solenoid "package" can also be added at a later date
to a continuous system.
Frigid-X™ Cabinet
Cooler Sizing Specifications
Contact Nex Flow Technologies
for assistance in sizing the Frigid-X Enclosure Coolers.
Below see Sizing Specifications for the Frigid-X Enclosure
Coolers.
| MODEL
NO. |
VERSION |
BTU/Hr.
cooling* |
| 61015 |
12
Continuous Operation |
1100 |
| 61025 |
12
Continuous Operation |
1800 |
| 61030 |
12
Continuous Operation |
2100 |
| 61040 |
12
Continuous Operation |
2900 |
| |
|
|
| 63015 |
NEMA
12 on-off control |
1100 |
| 63025 |
NEMA
12 on-off control |
1800 |
| 63030 |
NEMA
12 on-off control |
2100 |
| 63040 |
NEMA
12 on-off control |
2900 |
* Cooling effect based on 95
degrees temperature inside cabinet, 100 PSIG compressor inlet
pressure, and 70ºF inlet temperature.
BTU/hr. figures rounded to nearest 100 BTU/hr.
All Continuous Operation models include the cooling unit,
filter with auto drain and cold air distribution kit.
All On-Off control units
include the cooling unit, filter with auto drain, cold air
distribution kit, solenoid valve and thermostat.