Differential Pressure Switch

Differential Pressure SwitchThe Differential Pressure Switch model AFS-22 is a general purpose proving switch designed for HVAC and energy management applications. It may be used to sense positive, negative or differential air pressure.

The plated housing on the differential pressure switch contains a diaphragm, a calibration spring and a snap acting switch. The sample connections on each side of the diaphragm accept 0.25" O.D. metallic tubing via the integral compression ferrule and nut.

An enclosure on the differential pressure switch cover guards against accidental contact with the live switch terminal screws and the set point adjusting screw. The enclosure cover will accept a 0.5" conduit connection.

APPLICATION

The model AFS-22 is a general purpose proving switch designed for HVAC and energy management applications. It may be used to sense positive, negative or differential air pressure.

DESCRIPTION

The plated housing contains a diaphragm, a calibration spring and a snap acting switch. The sample connections on each side of the diaphragm accept 0.25" O.D. metallic tubing via the integral compression ferrule and nut. An enclosure cover guards against accidental contact with the live switch terminal screws and the set point adjusting screw. The enclosure cover will accept a 0.5" conduit connection.

MOUNTING

Select a mounting location which is free from vibration. The AFS-222 must be mounted with the diaphragm in any vertical plane in order to obtain the lowest specified operating set point. Avoid mounting with the sample line connections in the UP position. Surface mount via the two 3/16" diameter holes in the integral mounting bracket. The mounting holes are 3-7/8" apart.

AIR CONNECTION

The AFS-222 is designed to accept firm wall sample lines of 1/4" O.D. tubing by means of ferrule and nut compression connections. An optional adaptor suitable for slip on flexible tubing is available. For sample lines up to 10 feet, 1/4" O.D. tubing is acceptable. For lines up to 20 feet use 1/4" I.D. tubing. For lines up to 60 feet use 1/2" I.D. tubing. Locate the sample probe a minimum of 1.5 duct diameters downstream from the air source. Install the sampling probe as close to the centre of the air stream as possible.

Data Sheet
Installation & Operation

  | Back To Current Sensors

Search This Site

(Search by Product Type i.e. Level or Brand Name i.e. Walchem)


ENERCORP INSTRUMENTS LIMITED

About Enercorp

Enercorp Instruments Ltd is a Manufacturer of Temperature, Pressure & Humidity Instrumentation. Used for Industrial, Food Processing, Climate Monitoring & Energy Management Applications.

Sitemap

Enercorp Products

Our products include temperature, pressure, humidity & climate instruments for sensing, controlling, recording and indicating; as well as wind speed & direction systems, RTD elements, smokehouse probes & custom built RTD, thermocouple and thermistor temperature sensors, temperature transmitters/transducers, thermowells, moisture meters, signal conditioners, power supplies, air quality & gas monitors..

Contact Enercorp

  • Toll Free:
    1-800-363-2677
  • Telephone:
    416-231-5335
  • Fax:
    416-231-7662
  • Email and Website:
    sales@enercorp.com www.enercorp.com
  • Head Office:
    25 Shorncliffe Road,
    Toronto, ON
    M9B 3S4 Canada