Process Controls
|
|
|
|
Products
|
|
|
|
|
|
|
|
|
|
|
| |
|
Manufacturers
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
Intrinsically Safe Two Channel Relay
|
ISR2 Intrinsically Safe Two Channel Relay
- 2 Independent Relays
- Compact Design
- Contact or Probe Input
- Built-in De-bounce Delays
- Power and Output status LEDs
- Low Voltage Design for 12 or 24VAC/DC
- Din Mounting
- 12 or 24VDC Battery Back-Up
Two Channel Intrinsically Safe Relay
The ISR2 has two independent outputs to the hazardous area and two independent (dry contact) relay outputs. The outputs to the hazardous area can be switches or, when used with a conductive liquid, electrodes. When output "A" is completed (contact closed or low resistance), 0.5 second later the dry output contact "A" is closed and the "A" LED turns On. When output "A" is opened (contact opened or high resistance), 0.5 second later the dry output contact "A" opens and the "A" LED turns Off. "B" operates the same way, but is independent of "A." There is also a supply power LED indicator. The ISR2 must be located and grounded in a non hazardous location.
-
Electrical
Supply Voltage: 12 or 24 AC/DC ±10%
Power: 1.5 watts
Inputs: Switch Closure or Probe
Input Sensitivity: 10k - 100k
Pick-up & Drop-out Delays: 0.5 second
Max. Open Circuit Voltage: 7 volts
Max. Source Current: 0.1 milliamps
Output Rating @ 25°C:
5 Amps @ 125VAC
5 Amps @ 30VDC or 250 VAC
20,000,000 Mechanical Cycles
-
Physical
Mounting: Din Rail mount
Termination: Touch safe screw terminals,
with lift mechanism, #12 AWG max.
Weight: 10 Oz.
Ambient Temperatures
Operating: 0°C to 55°C
Storage: -40°C to 85°C
Two Channel Relay with Intrinsically Safe Inputs
|
|