Description
The Model 160B(R) Voltage Sensor is a single set-point voltage
sensor. Input voltages above the set-point cause the output
contacts to energize. Input voltages below the set-point cause
the output contacts to de-energize. The dead band between
pull-in and drop-out is less than 1%.
Wiring connections are made
to 1/4 quick connect terminals. Standard versions
have a 2-second restart delay. The R versions
of the Model 160B have a fixed 5-minute short cycle delay.
The Model 160B Voltage Sensor has a screwdriver adjustable
set-point range of approximately 35% of the maximum voltage.
The unit can be factory calibrated to meet specific requirements.
AC versions of the Model
160B Voltage Sensor are not frequency sensitive and may
be used in systems from 50 to 400 Hz. DC versions, or other
short cycle periods, are available on request.
|
|
Hot Features:
- Monitors for over
or under voltage
- Surface-mount package
- Optional 5-minute
time delay
|