Description
The Model 263 continuously monitors
3-phase power systems for phase loss, low voltage and phase
reversal. The monitor consists of a solid-state sensing circuit,
driving an electromechanical relay.
Applying correct voltage
and phase rotation energizes the relay. When properly adjusted,
a fault condition will cause the relay to de-energize, even
when regenerated voltage is present.
When the fault is corrected,
the Model 263 automatically resets. A manual reset version
and an option for gold-plated contacts are also available.
The Model 263 does not require
a neutral connection, and can be used on Wye or Delta systems.
Each of the five different voltage ranges is adjustable
to allow the monitor to be set for existing conditions.
NORMAL and TRIP LED indicators are provided to aid in adjustment
and system troubleshooting.
 |
•
Detects phase loss, phase reversal and low voltage
• 400Hz and gold contact
options
• Automatic or manual reset
• UL Recognized and CSA
Certified
|
Applications