Single
Input Gas Detection Monitor AirTest Model CT-1000
|
 |
 |
|
CT-1000
- Single Input Monitor
The CT-1000 is a single input
monitor for stand-alone applications. It can be supplied
with an onboard Carbon
Monoxide (CO), Combustible gas (Propane,
Natural
Gas), or Refrigerant (Halocarbon or Ammonia)
solid-state sensor. In addition to a power light, low alarm
light, and high alarm light, the monitor has two user settable
alarm relays and a time delay.
For use as a single channel controller the CT-1000 can be
supplied without an onboard sensor and factory configured
to accept 2 or 3-wire 4-20 mA input signals. The CT-1000
has been used extensively with electrochemical
Nitrogen Dioxide (NO2) sensors to detect diesel
exhaust.
Specifications |
Installation | Start-Up | Calibration |
Dimensions | Wire
Diagrams
|
 |
|
 |
|
Installation
- Separate the enclosure
lid from the body. There is a connector on the lid wiring.
- Locate a flat surface
to mount the enclosure so that the sensor can face downward.
- Mount the enclosure to
the wall using the two mounting hole locations.
- There is a power entry
location provided on the end opposite the sensor.
- Connect the electrical
fittings to the enclosure and bring in the electrical
wires. NOTE: BE SURE WIRING IS DONE ACCORDING TO THE LOCAL
ELECTRICAL CODE REQUIREMENTS.
- Connect the wires to the
removable connector blocks. Re-connect the enclosure lid.
|
|
 |
|
Start-Up
- If the unit is a 115 VAC
model apply power to AC HOT, AC NEUT & GND at TM1.
If the unit is a 24 VAC model apply power to AC HOT &
AC NEUT at TM1. The power LED will come on after about
5 seconds, as the sensor warms up. If the power LED does
not come on, then either the sensor is faulty, not connected
properly or there is no power to the sensor. The power
LED is actually monitoring the sensor output and is looking
for a minimum signal to be present.
- During the first minute
all alarms will activate and then de-activate
- Wait 24 hours before attempting
calibration of the unit. The relay connector may be disconnected
during this time.
|
|
 |
|
Calibration
SOLID STATE SENSORS:
The CT-1000 has been factory
calibrated and is ready for use. If however there is a level
of background gases, it should be calibrated on site. If
the range is to be changed, the CT-1000 must be re-calibrated.
NOTE: Wait 24 hours prior
to a cold start calibration. If the unit has been without
power for less than 20 minutes, then only a 10-minute wait
is required.
- Open the enclosure and
let the lid hang so that the LED indicator lamps can be
viewed. The lid can be removed by unplugging the LED indicator
lamp connector and using the internal relay indicator
lamps for calibration.
- Disconnect the relay connectors
(TM2, TM3) so that motors and/or alarms are not being
turned off and on during calibration.
- Set SW1, time delay setting
for alarm 1, to 0 (zero).
- Turning the alarm adjustment
potentiometers RV1 and RV2 clockwise will activate the
alarm relays, turning counterclockwise will de-activate
the alarm relays.
- Use a calibration flow
rate of 0.2 LPM (0.4 SCFH). Apply the gas mixture through
a humidifier for two minutes before adjusting the alarm
point. Note: The calibration mixture must be AIR based
not Nitrogen based.
- Through a humidifier (see
Calibration Kit drawing), apply a test gas mixture to
the sensor equal to the level required for the LOW alarm
point. Adjust alarm 1 clockwise (RV1) so that the relay
1 LED comes on. (Yellow LED on front cover).
- Through a humidifier (see
Calibration Kit drawing), apply a test gas mixture to
the sensor equal to the level required for the HIGH alarm
point. Adjust alarm 2 clockwise (RV2) so that the relay
2 LED comes on. (Red LED on front cover).
- Set time delay setting
for alarm 1 to desired setting. (SW1). Each number increment
adds approximately 2 minutes delay to the activation of
the alarm 1 relay. NOTE: During this time delay (when
activated), the indicator lamp for alarm 1 will flash.
- Connect the alarm relay
connectors (if removed) also the LED connector (if removed)
and install the enclosure lid.
Figure 1

Recommended humidifier arrangement
to be used when calibrating solid-state sensors.
|
|
 |
|
Dimensions
- Dimensional
Information
|
|
 |
|
Wire
Diagrams
-
CT-1000
Wiring Diagrams
|
|