Carbon
Monoxide Sensor AirTest Model TR-1000
|
 |
 |
TR-1000
- 4-20 mA Sensor / Transmitter
The
TR-1000, when equipped with the appropriate solid-state,
metal oxide (MOS) sensing element, can be used to detect
Carbon Monoxide (CO), Combustibles, and Refrigerant
gases. This sensor is generally used for monitoring areas
not continuously occupied, such as parking structures and
refrigerant compressor rooms.
Specifications
| Installation |
Calibration | Indicators,
Test Points & Potentiometers | Dimensions
| Wire Diagrams
|
 |
|
 |
|
Installation
- Locate
a flat surface to mount the enclosure so that the sensor
can face downward. If the rear power entry is to be used,
remove the plug before mounting the enclosure. The second
power entry is at the end opposite the sensor.
- Remove
the cover of the enclosure by removing the 4 screws in
the corners. Be careful here since the circuit board is
connected to the cover. The circuit board is also connected
to the sensor, so the cover will hang from these wires
when removed. Remove the plug from the end power entry
if it is to be used.
- Connect
the electrical fittings to the enclosure and bring in
the electrical wires. NOTE: BE SURE WIRING IS DONE ACCORDING
TO THE LOCAL ELECTRICAL CODE REQUIREMENTS. NOTE: To prevent
shorting problems do not leave ground wire to box bare
(if one is used) - cover with electrical tape.
- Connect
the wires to the removable connector block as shown on
the wiring drawing.
(See Fig.1)
|
|
 |
|
Calibration
SOLID
STATE SENSORS:
The
TR-1000 has been factory calibrated and is ready for use.
If however there is a level of background gases, it should
be calibrated on site. If the range is to be changed, the
TR-1000 must be re-calibrated.
- Connect
power and signal return wires to a suitable controller
that will provide sensor excitation and signal processing.
(See Fig.1)
For all the following readings TP1 (RED) is the COMMON
POSITIVE jack.
- Power
up the unit, the ready light will come on in 10 seconds.
Check TP2 (Black) for correct voltage of 5.0V ±0.1V. If
it is satisfactory let the sensor burn-in for 24 hours.
If voltage is unsatisfactory the board is faulty and must
be serviced.
- TO
SET ZERO Adjust the ZERO potentiometer, RV1, until the
ACTIVE LED (YELLOW) just goes off.
- TO
SET ZERO OFFSET Before proceeding, it is critical that
the sensor is exposed to clean air. If clean air cannot
be assured, a sample of clean air, or "Zero"
gas should be applied to the sensor. Monitor the OUTPUT
test point - TP3 (Yellow) - and adjust the ZERO OFFSET
potentiometer - RV3 - so the meter reads 0.4 volts (this
is equivalent to 4 mA). NOTE: The 4 to 20 mA loop must
be complete.
- TO
SET SPAN While still monitoring the OUTPUT test point
- TP3 (Yellow), apply a sample of gas consisting of the
target gas mixed with air. The concentration of the gas
should be the same as the desired full scale of the TR-1000.The
flow rate of the gas must be 0.2 liters/minute. Adjust
the "GAIN" trimpot - RV2 - so the meter reads
2.0 volts. (This is equivalent to 20 mA). Note: apply
the gas through a humidifier (see Calibration Kit drawing).
The mixture must be AIR based not Nitrogen based.
It
is recommended that sensor calibration be carried out on
an annual basis.
Figure
1

Figure
2
|
|
 |
|
Indicators,
Test Points & Potentiometers
- The
ready, green LED, indicates that power has been correctly
applied.
- The
active, yellow LED When "ON" indicates the sensor
output is in the active area. When "OFF" indicates
the sensor output is below zero or overrange.
- Test
Points are:
- RV1
-ZERO potentiometer
- TP1
(Red) -COMMON reference point for TP2,TP3 & TP4,
voltmeter POSITIVE connection.
-
TP2 (Black) 5V ±0.1v, circuit power.
-
TP3 (Yellow) -OUTPUT VOLTAGE, 0.4 to 2.0 volts (equates
to 4-20 mA).
-
TP4 (White) -SIGNAL test point, typically 0.0 to 1.6
volts.
- Potentiometers:
- RV1
-ZERO potentiometer
- RV2
-GAIN potentiometer
- RV3
-ZERO OFFSET potentiometer
Figure
3
Recommended
humidifier arrangement to be used when calibrating solid-state
sensors
|
|
 |
|
Dimensions