Toxic
Gas Sensor AirTest Model TR-3200
|
 |
 |
|
TR-3200 - 4-20 mA Sensor / Transmitter
The
TR-3200 is a Toxic Gas Sensor that uses electrochemical
cell technology as the sensing element. It is available
in a variety of toxic gases such as
Nitrogen Dioxide (NO2), a product of diesel exhaust;
Ammonia
(NH3), used as a refrigerant;
Carbon Monoxide (CO), a product of combustion;
ppm
Hydrogen (H), battery off-gas; and others.
Specifications
| Installation |
Calibration | Dimensions
| Wire Diagrams
|
|

|
|
|
|

|
|
Installation
-
Locate
a flat surface to mount the enclosure using the mounting
feet provided.
The power entry is at the bottom of the enclosure.
-
Remove
the cover of the enclosure by removing the 4 screws
in the corners. Be careful here since the circuit board,
including sensor, is connected to the cover. The complete
assembly can be set aside while wiring is installed.
-
Connect
the electrical fittings to the enclosure and bring in
the electrical wires. NOTE: BE SURE WIRING IS DONE ACCORDING
TO THE LOCAL ELECTRICAL CODE REQUIREMENTS.
-
Connect
the wires to the terminal block as shown on the wiring
drawing.
(See Fig.1)
|
|
|
|

|
|
Calibration
Figure
1

-
Connect
the TR-3200 unit to a controller, one wire to + and
the other to the 4-20 mA Loop Return (-). Power-up the
unit. TP4 (Black) is the COMMON REFERENCE for all voltage
measurements. A high impedance DVM must be used.
-
Sensor
Bias Voltage. APPLIES TO NH3, HCL AND NO SENSORS ONLY.
The bias voltage has been factory set but can be checked.
(Bias voltage test point is tab at 10:00 o'clock position
on sensor - see Fig. 1 above).
The reading is: 0.250V for NH3; 0.300V for HCL; 0.200V
for NO
-
Monitor
Signal Test Point TP2 (Yellow) and adjust the ZERO POT
(RV1) so the meter reads Zero (0 +/- .001V) (Calibration
area free of gas or Zero Gas applied).
-
Monitor
the Output Test Point TP3 (Red) and adjust the OFFSET
POT (RV3) so the meter reads -0.04V. (A current meter
in the power line loop will read 4 mA.)
-
While
still monitoring the Output Test Point TP3 (Red), apply
test gas to the sensor. (Flow rate1.0 LPM for NO2/HCL/CL2
otherwise 0.5 LPM). Wait until the reading stabilizes.
-
Adjust
the GAIN POT (RV4) so the "Test Gas to Range"
Ratio is in proportion to the Maximum Output Current.
See formula below. There is some interactivity and it
will be necessary to repeat steps 3 - 5 until no change
is noted in the offset reading
(-0.04V)