Specifications
|
Installation
|
Temperature
Probes |
|
|
- Accuracy:
± 0.3°C
Repeatability: 0.1°C
- Choice
of 2 mechanical configurations
and large choice of probes to suit all applications
- Available
as 2-wire loop powered units
or as 3-wire units
- On-site
calibration without interruption
of the output signal
- Modular
design facilitates installation
and maintenance
- NEMA
12 enclosure
|
Specifications
Note: Range of output signal is limited to a maximum span of 110°C
/ 200°F
| Model |
Installation
Type |
Circuit
Type
Supply Voltage |
Output
Signal |
Standard
Ranges |
Temp.
Limits
at probe |
Dimensions
|
| TL1-2C-XXB |
wall
through wall |
2-wire,
loop powered
10VDC + 0.05 x Load |
4-20
mA |
0..100°F,
0..200°F
-30..70°C, 0..100°C
consult factory
for other ranges
(see note above) |
see
probes |
154
x 72.5 x 48 mm
Macrolon Case
400 / 420 g |
| TL1-3C-XXB |
3-wire
10..35VDC / 24 VAC |
4-20
mA |
| TL1-3V-XXB |
0-5
V |
| TL1-2C-R2B |
duct
mount |
2-wire
10VDC + 0.05 x Load |
4-20
mA |
max.
160°C |
| TL1-3C-R2B |
3-wire
10..35VDC / 24 VAC |
4-20
mA |
| TL1-3V-R2B |
0-5
V |
Installation
|
Modular
Design for Simple, Problem Free Installation
and Easier Maintenance
Each
TL series transmitter consists of a base plate and a measurement
module (electronics, probe and sensors). The transmitters
are calibrated at our factory and are shipped in an individual
box for protection during shipment or storage.
Installation
is a simple 2-step process:
|
 |
Step
1
The base plate is mounted and wired
(a standard electrical box may be used in the case of a wall
installation). Since the measurement module is not required
during this part of the installation, it can be safely stored
until all the work is completed. |
 |
Step
2
Upon completion of the wiring work, the module is just
snapped into the base plate and secured with the screws provided.
Any module can be installed with any base plate, no special
matching is required.
When it is time to re-certify calibration or if a repair
is required, simply replace the module. Rehabilitated, fully
calibrated and certified replacement modules are available
from RIC. |
Temperature
Probes
( Pt100 RTD
for TL transmitter series)
Specifications
( Pt100 RTD for TL transmitter series)
| Model |
Description |
Measuring
Range |
Material |
Dimensions/
Notes |
| AC1909 |
Fast
response air probe
Use for wall mount installation
(area temperature) |
-50..200°C
/ -58..392°F |
DIN
1.4401
Pt100 Class A |
100
x 6 mm
plugs directly on TL1-xx-XXB
or TL1-xx-R2B transmitter |
| AC1900 |
Air
probe |
-70..300°C
/ -94..572°F |
DIN
1.4401
Pt100 Class A |
100
x 3 mm
plugs directly on TL1-xx-R2B transmitter |
| AC1903 |
Air
probe with 2m (6 ft) cable |
-70..500°C
/ -94..932°F |
DIN
1.4401
Pt100 Class A |
200
x 6 mm
use with TL1-xx-XXB |
| AC1904 |
Short
air probe with 2m (6 ft) cable |
-50..120°C
/ -58..248°F |
DIN
1.4401
Pt100 Class A |
50
x 6 mm
use with TL1-xx-XXB |
| AC1905 |
Surface
probe with 2m (6 ft) cable |
-70..300°C
/ -94..572°F |
Bronze
Pt100 Class A |
mounting
hole for screw
use with TL1-xx-XXB |
AC1910
AC1911
AC1912 |
Air
probe with 1/4" G mounting adapter and 2m (6 ft) cable |
-70..500°C
/ -94..932°F |
DIN
1.4401
Pt100 Class A |
diameter:
3 mm
immersion depth:
AC1910: 30 mm
AC1911: 50 mm
AC1912: 100 mm
use with TL1-xx-XXB |

|