Conductivity,Node,Sensor,Tee,Model,NCKT

Conductivity Node With
Sensor and Tee Model NCKT


Conductivity Node With Sensor and Tee Model NCKT
NCKT Conductivity Node With Sensor and Tee
Product Information

The NCKT is a LONWORKS* conductivity node in a NEMA 4X enclosure with a 4 electrode conductivity sensor and a quick release sensor tee. The NCKT is primarily used in cooling tower applications, but may be used in many process applications.

Osmonics® Lakewood Instruments 4-electrode sensor with temperature compensation is ideal for applications where sensor fouling may occur. The 4-electrode design measures voltage and current across four titanium electrodes and compensates for any contamination build up on the electrodes. When too much fouling occurs, or the sensor wiring is broken, a fouled sensor alarm is generated, notifying the user.

Specifications

Sensor
Enclosure
Type:
4-electrode
Type:
NEMA 4X
Range:
0-100,000 µS
Fittings:
½ inch NPT to controller Strain relief to sensor
Sensor Tee
Fittings:
¾ inch solvent weld
Materials:
CPVC
NODE
Max Temp
140°F (60°C)
Type:
Conductivity
Pressure:
140 psi @ 100°F
(9.7 bar @ 38°C)
Power:
24 VDC

* LonWorks is a registered trademark of Echelon Corporation.

Conductivity Node With
Sensor and Tee Model NCKT


Site Designed And Maintained By Panther Marketing And Design