| Inputs |
|
|
| Power |
|
80-300 VAC |
| Sensor |
|
2 or 4 electrode Conductivity
and ORP glass Electrode w/BNC |
| Temperature
comp. |
|
None, 500 NTC, 4K
NTC, 10K NTC, 100 PTC, 1K PTC,
3K PTC and 10K PTC |
| Flow / level switch |
|
Dry contact |
| Water Meter Input |
|
Two contacting head
or open collector |
|
|
|
| Outputs |
|
|
| Relays |
|
3 Amps @ 120 VAC |
| 4-20 mA |
|
Two, isolated w/-35L |
|
|
|
| Controller |
|
|
| Conductivity Range |
|
0-100,000 µS (varies
with sensor) |
| Conductivity Accuracy |
|
±40 µS |
| Conductivity Resolution |
|
10 µS |
| ORP Range |
|
-1000 to +1000 mV |
| ORP Accuracy |
|
±5 mV |
| ORP Resolution |
|
1 mV |
| Deadband |
|
Adjustable |
| Setpoints |
|
Direct or Reverse
(field configurable) |
| Feed timer |
|
Adjustable |
| Keypad |
|
Numeric |
| Display |
|
Illuminated 128 x
64 pixel LCD |
| Ambient Temperature |
|
32-158°F (0-70°C) |
| Enclosure |
|
ABS Plastic |
|
|
NEMA-4X Optional |
| 2430P |
|
LonWorks Technology-based
controller with 4 selectable relays for HIGH/LOW setpoints
or alarms. Requires ORP and conductivity sensor (530,
540, or 543) which must be ordered separately. Controller
has no power cord, outlets or plumbing. |
| CONTROLLER
OPTIONS (optional; select no more than three) |
| -RTC |
|
Schedule feed timer
with 28-day programmable clock for selectable relays. |
| -35L |
|
Two 4-20 mA output
configurable for remote data acquisition of ORP and
conductivity. |
| -RS2L |
|
Communications node
with the LRWS program; requires -RTC
Option. |
| -NIN |
|
Network interface
node; allows 1 NRLY and/or up to 3 NCON/NCKTs
to be added. |
| ENCLOSURE
OPTIONS (optional) |
| -DU |
|
Duplex outlet for
chemical pump, power cord. |
| LANGUAGE
OPTIONS (optional, choose one, English and Spanish
Standard) |
| -EF |
|
English and French. |
| -EG |
|
English and German. |
| REMOTE
NODE OPTIONS (optional; MUST purchase -NIN Option
above) |
| NRLY |
|
Four additional relays
with enclosure (1 per 2000 Series Controller). |
| NCON |
|
Conductivity node
(node only). |
| MOUNTING
OPTIONS |
| PM |
|
Panel mount 6¼ inch
square cutout. |
| BM |
|
Bracket for pipe mounting. |
| SOFTWARE
AND EXTERNAL MODEMS |
| LRWS |
|
Windows-based
software for computer to communicate with 2000 Series
Controllers. |
| MD4X |
|
High-Baud modem in
NEMA-4X enclosure ready to power. |
| MD |
|
High-Baud modem for
use with 2000 Series Controllers. |