pH,200,Controller,Oakton,Instruments

pH 200 Controller from Oakton Instruments

pH 200 Controller

Scrolling, 14-segment LED guides user through set-up functions

pH,200,Controller,Oakton,Instruments

pH,200,Controller,Oakton,Instruments
Two set point, two SPDT relay for on/off control
pH,200,Controller,Oakton,Instruments
Reliable power supply from 85 to 250 V AC/DC withstands voltage fluctuations
pH,200,Controller,Oakton,Instruments
Two separately adjustable hysteresis bands prevents rapid contact switching at either set point
pH,200,Controller,Oakton,Instruments
Selectable symmetrical mode operation eliminates electrical noise
pH,200,Controller,Oakton,Instruments
Two-point pH calibration; offset ORP and temperature calibration
pH,200,Controller,Oakton,Instruments
4-20 mA output for remote monitoring or hard copy recording
pH,200,Controller,Oakton,Instruments
Two level password protection for calibration and setup parameters
pH,200,Controller,Oakton,Instruments
Toggle between pH (or mV) and temperature display
pH,200,Controller,Oakton,Instruments
Removable terminal strips offer quick and easy connections
pH,200,Controller,Oakton,Instruments
Battery back-up of memory maintains set-up if power fails

These sturdy, compact controllers withstand voltage fluctuations from 85 to 250V AC/DC! They are ideal for installation were electrical fluctuations are common, or install them in series throughout areas of differing electrical conditions.

Advanced setup mode lets you set relay values, select pH or ORP control, select manual or automatic temperature compensation, and more. It also lets you view electrode slope and offset, and previous calibration points.

The 1/8 DIN housing is ready to install in standard panels and NEMA rated boxes. Includes mounting hardware; accepts electrodes with BNC connectors and 100 Pt RTD ATC elements.

Click below to download Acrobat (.pdf) file of:
pH,200,Controller,Oakton,Instruments pH 200 controller Product Bulletin
pH,200,Controller,Oakton,Instruments pH 200 Controller Manual

Measures
pH, mV, °C
pH Range
0.00 to 14.00 pH
pH Resolution
0.01 pH
pH Accuracy
±0.01 pH
pH Calibration
up to 2 points (1.68, 4.01, 6.86, 7.00, 9.00, 10.00, 12.45)
mV Range
±1000 mV
mV Resolution
1 mV
mV Accuracy
±2.0 mV
mV Calibration
offset up to ±150 mV
Temperature Range
-10.0 to 110.0°C
Temperature Resolution
0.1°C
Temperature Accuracy
±0.5°C
Temperature Calibration
offset to ±10°C
Control type
on/off
Number of inputs
one
Number of set points
two (high and low)
Separate alarm relay
no
Output Control
2 SPDT nonpowered relays, 6A at 110 VAC; 250 VAC max.
Output Current
4 to 20 mA output, isolated
Hysteresis
adjustable; 0.0 pH to 2.0 pH or 0 to 300 mV
Input impedance
10^12
Temperature Sensor
2 or 3 wire 100W Pt RTD
Temperature Compensation
Automatic or manual, from 0 to 100°C
Password protection
two level (calibration and setup parameters)
Display
scrolling 14-segment LED, four digit
Operating Temperature
0 to 50°C, 10 to 95% RH
Housing
1/8 DIN
Dimensions
48 x 96 x 150 mm; panel mount 91 x 45 mm
Shipping weight
3 lb (1.4 kg)


Back to pH Controllers