Application
The general purpose two-wire ultrasonic transmitter provides non-contact level measurement up to 40' or 12.2m, and is ideally suited for challenging corrosive, coating or waste liquids. The transmitter is broadly selected for atmospheric bulk storage, day tank, process vessel and waste sump applications. Media examples include ink and polymer. See the LU12-14 sensor application matrix for more details.
Specifications
Range: LU12: 0.16' to 10' (5 cm to 3m)
LU13: 0.33' to 25' (10 cm to 7.6m)
LU14: 0.66' to 40' (20 cm to 12.2m)
Accuracy: ± 0.15% of span in air
Resolution: 0.125" (3 mm)
Beam width: LU12: 2" diamater
LU13 or 14: 3" diameter
Dead band: LU12: 0.16' (5 cm)
LU13: 0.33' (10 cm)
LU14: 0.66' (20 cm)
LED indication: Power, calibration
and diagnostics
Memory: Non-volatile
Supply voltage: 14-28 VDC
Loop resist.: 600 Ohms @ 24 VDC
Signal output: 4-20 mA, two-wire
Calibration: Target, calibration wire
Fail-safety: Reverts to 22 mA
Process temp.: F: -40° to 160°
C: -40° to 71°
Temp. comp.: Automatic
Electronics temp.: F: -40° to 160°
C: -40° to 71°
Pressure: 30 psi (2 bar) @ 25° C., derated
@ 1.667 psi (.113 bar) per °C. above 25° C.
Enclosure rating: NEMA 6X (IP67)
Installed height: 1.7" (4.3 cm) above
tank process mount
Encl. material: PC/ABS FR
Trans. material: PVDF Kynar®
Cable jacket mat.: Polypropylene
Cable type: 3-conductor, shielded
Cable length: 10' (3m)
Process mount: LU12: 1" NPT (1" G)
LU13 or 14: 2" NPT (2" G)
Mount. gasket: Viton® (G version only)
Classification: General purpose
CE compliance: EN 50082-2 immunity
EN 55011 emission
Click here to download above specifications in a PDF file format.

Click here to download above Manual in a PDF file format.
 
Technology
General Purpose Yes
Conductive Yes
Non-Conductive Yes
Δ Conductive Yes
Non-contact Yes
Clean Yes
Dirty Yes
Coating Yes
Non-coating Yes
Ambient pressure Yes
Low pressure Yes
Foam Consult Factory
Vapors Consult Factory
Δ Gas density Consult Factory
Intrinsically safe No
Medium pressure No
Integral Relay No
Contact No
Vacuum No