Enclosure,Cooler,Systems

Enclosure Cooler Systems

Enclosure Cooling

• Vortex Cooler TM Enclosure Coolers
• VorCool™ Enclosure Cooler System
• Cold Pump® Cooling System

• Open Sizing And Selection Interactive Excel Worksheet


Vortex Cooler™ Enclosure Coolers

Today's compact, multi-function electronic controls, variable speed drives and servos are extremely sensitive to heat and contamination while their confined enclosures make temperature control difficult.

Excessive heat causes components to cook, digital displays to misread, starters and breakers to trip below rated loads and controls to drift.

Fans often provide inadequate cooling and commonly pull in dirty, humid air creating another source of failure.

ITW Vortec's Vortex Cooler™ Enclosure Coolers are the low-maintenance alternative for keeping enclosures cool and clean -- without Freon or other refrigerants.
Vortex Cooler System
Figure 1. Vortex Cooling System
 
Features:
  • Eliminate downtime caused by dirty, overheated controls.
  • Replace hot, dirty air in the enclosure with cool, clean air.
  • May be thermostatically-controlled to operate only when necessary to save energy.
  • Use a vortex tube to generate cold air without Freon or other refrigerants (CFCs/HCFCs).
  • Compact size, easy to install.
  • Exceptionally reliable, no moving parts to break.
  • Maintenance-free, no compressors or filters to clean.
  • Maintain NEMA 4, 4X and 12 ratings.
  • Cooling capacities up to 5000 BTUH (1250 kcal/H).

 


Prevent downtime from overheated,
dirty controls with Vortex Coolers.

Models:

All models listed below include a 5-micron filter.

MODEL No.

 
With
Thermostat*
Without
Thermostat
Capacity
Air Consumption
Thermostat
Nema Type
BTUH
KCAL/H
SCFM
SLPM
Factory Set
750 760 400 101 8 227 90ºF ± 2º/32ºC ± 1º 12
740 730 900 225 15 425 90ºF ± 2º/32ºC ± 1º 12
790 780 1500 378 25 708 90ºF ± 2º/32ºC ± 1º 12
770** -- 1500 378 25 708 80-122ºF/27-50ºC 12
795 785 2500 625 35 991 90ºF ± 2º/32ºC ± 1º 12
7970 7870 5000 1250 70 1981 90ºF ± 2º/32ºC ± 1º 12
797 787 1500 378 25 708 90ºF ± 2º/32ºC ± 1º 4
797SS 787SS 1500 378 25 708 90ºF ± 2º/32ºC ± 1º 4X

* See Figure 1 for components included with these systems.

**Provides rough thermostatic control with a non-adjustable thermostat -- electrical connections are not required.



Back To Top
 

VorCool™ Enclosure Cooling System

VorCool™ takes enclosure cooling to new heights by adding temperature monitoring and alarm capabilities to the Vortex Cooler.
All components are housed in a compact enclosure designed for easy installation.

Features:

  • LED enclosure temperature display.

  • Visual alarm and remote alarm relay.

  • User-adjustable thermostat control.

  • 1500 BTUH (378 kcal/H).

Models:

MODEL No.

Input Voltage

Frequency

Temperature Display

796-1

110

60

Fahrenheit

796-6

220/240

50/60

Celsius




Back To Top


Cold Pump® Cooling Systems

Our Cold Pump® Cooling Systems continuously re-circulate and cool air inside control cabinets to keep out dirt and dust. Cold Pumps feature a closed-loop design and use CFC-free HFC-134a coolant. Cold Pumps are designed for easy retrofit installation and operate on 115V/60Hz single phase power.

 

Models:

 

CAPACITY

ROOM TEMPERATURE
OPERATING REQUIREMENTS

MODEL NO.

BTUH

kcal/H

515*

1500

378

50ºF - 110ºF (10ºC - 43ºC)

560T

6000

1512

70ºF - 125ºF (21ºC - 52ºC)

* Specify top, right side or left side installation.



Back To Top


Vortex Enclosure Cooler Systems