One,Series
5320 BRADCO BLVD
MISSISSAUGA ON L4W 1G7
Tel: 905 625 5082
Fax: 905 625 5709

One Series


Technology

Unique I AM WORKING™ function
The One Series provides a continuous indication of its health AND the switch output status, both locally and remotely. An LED on the front panel and a discrete logic output signal are used to communicate three states:

  • I AM WORKING™ but I Have Not Switched
  • I AM WORKING™ and I Have Switched
  • I Am Not Working
The One Series I AM WORKING™ feature diagnoses the health of the sensor, software, microprocessor and power supply. And it does all this on a continuous basis. Used in conjunction with the standard switch output, the I AM WORKING™ signal can even help satisfy many DPDT requirements. Functions of the I AM WORKING™ signal are as follows:

Signal
Interpretation
I AM WORKING™ output "On" continuously
Normal operation, unit operating properly
I AM WORKING™ output pulsed "On" and "Off"
Beyond set point, unit operating properly
I AM WORKING™ output "Off"
Loss of power or unit inoperable


100% Set point and deadband adjustment

Set point and deadband values are adjustable over the full range span using a convenient, simple to operate, front panel keypad. Access to the programming mode requires a simple, yet tamperproof, keying sequence... It's better than password protection!

Process variable extremes stored in non-volatile memory
System pressure or temperature extremes are retained in the One Series' non- volatile memory, assisting in troubleshooting problems. The One Series captures high and low pressure or temperature extremes constantly.

Unique switch operating mode
The One Series provides four convenient switch operating modes which determine the function of the switch output, deadband, LED status indicator and I AM WORKING™ signal. The desired switch operating mode can be selected from one of four options:

  • High Limit Alarm - Close on Rise
  • High Limit Shutdown - Open on Rise
  • Low Limit Alarm - Close on Fall
  • Low Limit Shutdown - Open on Fall
Excellent media compatibility
Pressure: Wetted materials include a 316 stainless steel pressure connection, ceramic pressure sensor and your choice of O-ring material. The piezoresistive ceramic sensor is compatible with most media except a few aggressive acids. Temperature: 304 stainless steel sensor housing.


Back to top

Specifications

Patent Pending
(Specifications at 25°C and nominal voltage unless otherwise noted)

Mechanical:
Enclosure Specifications:
Die cast aluminum epoxy powder coated; NEMA 4X (except "R" temperature models. "R" models are weather tight but do not carry a specific NEMA rating.)
Pressure Ranges:
0 to 4000 psi. See Model Charts
Wetted Materials:
Process connection: 316 stainless steel

Sensor: Ceramic (96% Alumina)

O-Ring: Viton is standard. See How To Order for other materials

Temperature Ranges:
-50 to 1000°F (-45.6 to 537.8°C) See Model Charts
Sensor Housing:
304 stainless steel
Extension Wire:
Model H: MI extension wire: 0.125" OD x 6, 10 or 20' long

Model R: Teflon® jacketed cable, Teflon® coated leads with stainless steel over braid, 6', 10' or 20' long

Weight:
Single enclosure units: 1 3/4 lbs (0,8 kg)
dual enclosure units: 2 1/2 lbs (1,1 kg)
Shock:
MIL-STD-810E, Method 516.4; 10 mSec @ 15 g's, 6 mSec @ 40 g's; 3 times each axis
Vibration:
MIL-STD-810E, Method 514.4; 10-2000 Hz @ 0.04 PSD (equates to 8 g's @ 2000 Hz)

Electrical:
Conduit Connections:
Single enclosure (switch rating A): 1/2" NPT female sealed conduit connection

Dual enclosure (switch rating B and C): 1/2" NPT female conduit connection. Optional dual 1/2" NPT female conduit connections

Dual enclosure (switch rating D): dual 1/2" NPT female conduit connections

Electrical Connection:
Single enclosure (switch rating A): 1 meter wire harness, 20 AWG, PVC jacketed, shielded cable

Dual enclosure (switch rating B and C): terminal block, accomodates 20 to 14 AWG conductors

Dual enclosure (switch rating D): separate terminal blocks for high and low voltage signals, accomodates 22 to 14 AWG conductors

Power Source:
24 VDC nominal; 18 to 30 VDC, 100 mA maximum (surge protected); optional 115 VAC nominal, ± 10%
Switched Output:
Switch rating A & B: 100 mA @ 5 to 30 VDC, SPST MOSFET, open drain (collector) sinking output, short circuit protected

Off state leakage current 10 µA @ 30 VDC, fail safe "open"

Switch rating C: 15 Amp @ 24-280 VAC, SPST, solid-state relay; minimum load current is 150 mA

Off state leakage current 0.1 mA @ 280 VAC, fail safe "open"

Switch rating D: 5 Amps @ 115 VAC. SPST, solid state relay minimum load current is 150 mA.

Off state leakage current is 0.1 mA @ 115 VAC, fail safe "open"

I AM WORKING™ Output:
100 mA @ 5 to 30 VDC, MOSFET, open drain (collector) sinking output, short circuit protected

SPST off state leakage current 10 µA @ 30 VDC, fail safe "open"

Optional Analog Output:
4 to 20 mA sourcing output, non-isolated, proportional to sensor input range, load resistance 500W maximum
EMI/RFI:
Complies with CE EMC requirements EN50081-1, EN50082-2 (switch rating B and C only)
Emission:
Conducted emission EN55011 class A; Radiated emission EN55011 class A
Immunity:
Electrostatic discharge EN61000-4-2; Conducted disturbances (RF) acc. IEC 1000-4-6

Radiated E-fields (RF) acc IEC 1000-4-3, acc ENV50204

Surge withstanding IEC 1000-4-5; Transient withstanding EN 61000-4-4

Operating:
Pressure Ranges:
See Model Charts
Temperature Ranges:
See Model Charts
Set Point:
Adjustable over the full range span. See Model Charts
Deadband:
Adjustable over the full range span. See Model Charts
Maximum Over Range:
See Model Charts. N/A for temperature ranges
Burst Pressure:
See Model Charts. N/A for temperature ranges
Set Point Repeatability:
±0.2% of maximum range value
Accuracy:
Switch point/indication: ±1.0% of maximum range

Analog output: ±1.0% of maximum range

Media Temperature Effects:
±1.0% of maximum range from 32 to 158°F (0 to 70°C)
Long-Term Stability:
±0.25% of range per year, maximum
Switch Response Time:
25 mSec typically, 200 mSec maximum

General Features:
Ambient Temperature:
Operating: -22 to 158°F (-30 to 70°C)

Storage: -22 to 176°F (-30 to 80°C)

Media Temperature For Temperature Models:
Limited by O-ring material. See How to Order
Media Temperature For Temperature Models:
-94 to 550°F (-70 to 288°C)

-94 to 1150°F (-70 to 621°C)

Local Digital Display:
2 Row by 16 character LCD display for indication of programming parameters and process variable; also displays extreme (min/max) pressure or temperature values
Output Status LED:
Local LED to indicate switch and I AM WORKING™ output status
Field Accessible Programming:
Convenient keypad allows for easy product configuration and adjustment
Memory:
All programmed data stored in non-volatile memory (saved when power lost)
I AM WORKING™ States:
Signal
Interpretation
I AM WORKING™ output "On" continuously

I AM WORKING™ output pulsed "On" and "Off"

I AM WORKING™ output "Off"

Normal operation, unit operating properly

Beyond set point, unit operating properly

Loss of power or unit inoperable


Approvals:
  • UL Listed, cUL Certified
  • Class I, Division 2, Groups A, B, C, D
  • Class II, Division 2, Groups F, G
  • Class III; Enclosure type 4X (except "R" temperature models)
  • Class I, Zone 2, Group IIC T4
  • CE EMC Directive (standard on switch rating B & C. N/A on switch relay A and D)


Back to top

Model Charts

Sensor Type 1, ½" NPT Female, 316 stainless steel pressure connection, Viton O-ring, piezoresistive ceramic pressure sensor

Model
Pressure Range
Deadband
Maximum
Over Range

Burst Pressure
   

 

The difference above or below set point at which the switch resets to normal operation
The value at which the sensor may experience irreversible damage
The value at which the sensor may rupture
Low
High
psi/bar
psi
bar
psi
bar
psi
bar
A
0
25
1,7


Fully adjustable from 0% to 100% of range


50
3,4
100
6,8
B
0
50
3,4
100
6,8
200
13,6
C
0
125
9
250
18
500
36
D
0
250
17
500
34
1000
68
E
0
700
48
1400
96
2800
192
F
0
1400
96
2800
192
5600
384
G
0
2800
193
5600
386
11200
772
H
0
4000
276
8000
552
16000
1104


Sensor Type 2, 0.25" OD sensor housing, 304 stainless steel, 100 ohm RTD temperature sensor

Model
Temperature Range
Deadband
Maximum
Over Range

Description
    The difference above or below set point at which the switch resets to normal operation
The value at which the sensor may experience irreversible damage
 
L1
-50 TO 450°F
-45 TO 232°C


Fully adjustable from 0% to 100% of range


550°F
288°C
Local sensor, 4" long
L2
-50 TO 450°F
-45 TO 232°C
550°F
288°C
Local sensor, 8" long
L3
-50 TO 450°F
-45 TO 232°C
550°F
288°C
Local sensor, 10" long
R1
-50 TO 450°F
-45 TO 232°C
550°F
288°C
Remote sensor, 6" long with 6' Teflon® extension wire
R2
-50 TO 450°F
-45 TO 232°C
550°F
288°C
Remote sensor, 6" long with 10' Teflon® extension wire
R3
-50 TO 450°F
-45 TO 232°C
550°F
288°C
Remote sensor, 6" long with 20' Teflon® extension wire
H1
-50 TO 1000°F
-45 TO 538°C
1150°F
621°C
Remote sensor, high temperature, 2.5" long with 6' MI extension wire
H2
-50 TO 1000°F
-45 TO 538°C
1150°F
621°C
Remote sensor, high temperature, 2.5" long with 10' MI extension wire
H3
-50 TO 1000°F
-45 TO 538°C
1150°F
621°C
Remote sensor, high temperature, 2.5" long with 20' MI extension wire

 

Sensor Type 3, 1/4" NPT female pressure connections, silicon sensor with aluminum/plastic/glass/RTV wetted parts. Suitable for sensing of dry air and inert gas.

Model
Differential
Pressure
Range

Deadband
Maximum
Differential
Pressure

Maximum
Working
Pressure

Differential
Burst
Pressure

K1
0 - 5" wcd
(12,4 mbar)


Fully adjustable from 0% to 100% of range


1 psid
(0,1 bar)
6 psig
(0,4 bar)
5 psid
(0,3 bar)
K2
0 - 25" wcd
(62,2 mbar)
20 psid
(1,4 bar)
100 psig
(6,9 bar)
50 psid
(3,4 bar)
K3
0 - 80" wcd
(199 mbar)
20 psid
(1,4 bar)
100 psig
(6,9 bar)
50 psid
(3,4 bar)
K4
0 - 5 psid
(344,7 mbar)
30 psid
(2,1 bar)
100 psig
(6,9 bar)
80 psid
(5,5 bar)
K5
0 - 12 psid
(827,4 mbar)
60 psid
(4,1 bar)
100 psig
(6,9 bar)
120 psid
(8,3 bar)
K6
0 - 35 psid
(2,41 bar)
0 - 100 psid
(6,9 bar)
100 psig
(6,9 bar)
120 psid
(8,3 bar)


Back to top

How to Order

Build a part number by selecting appropriate code for each feature category.
Example: D1A1B2NM446


D
1
A
1
B
2
N
M446
Setting/
Indication
Method
Series Designation
Switch Rating/
Termination
Sensor Type
Model
*O-Ring Material
Auxiliary Output
Option(s)

*Not applicable for temperature sensors

COMP0NENTS CODE
DESCRIPTION
Setting/Indication Method
D
User adjustable, digital indicating configuration
Series Designation
1
Designation for One Series product line
Switch Rating/Termination
A
Open drain (collector) output with flying lead-wires
B
Open drain (collector) output with terminal block (upper enclosure included)
C
15A solid-state relay with terminal block (upper enclosure included)
D
5A solid-state relay with 115 VAC internal power supply and terminal
Sensor Type
1
Pressure, 316 stainless steel 1/2" NPT female, pressure connection, ceramic sensor
2
Temperature sensor
3
Differential pressure (dry air, inert gas)
Model
A,B,C,D,
See Model Charts
E,F,G,H,
L1,L2,L3,
R1,R2,R3,
H1,H2,H3
K1,K2,K3
K4,K5,K6
O-Ring Material (Not applicable for temperature sensors)
0
Viton; media temperature 0 to 257°F
(-17 to 125°C)

1
Aflas; media temperature 32 to 200°F
(0 to 93°C)

2
Buna N; media temperature -22 to 257°F
(-30 to 125°C)

3
EPR; media temperature -22 to 257°F
(-30 to 125°C)

4
Kalrez; media temperature 32 to 257°F
(0 to 125°C)

Auxiliary Output
N
None
A
4 to 20 mA analog process signal
Option(s)
M025
5A, 200VDC(max.) Relay Output
M026
Low Current and Inductive Load Switching SSR
M027
VAC Power Supply with Free SSR Contacts
M201
Factory set parameters
(set point, deadband and switch operating mode)
M205
Scale 4 to 20 mA Output
(Factory Configured, Customer Specified)
M270
Display and nameplate units of measure in degree C (temperature units only)
M276
Display and nameplate units of measure in bar (pressure units only)
M277
Display and nameplate units of measure in kPa (pressure units only)
M278
Display and nameplate units of measure in kg/cm2 (pressure units only)
M440
Cover chain
M444
Paper tag
M446
Stainless steel tag
M550
Oxygen service cleaning; may require Viton O-ring (pressure units only)
M905
1/2" NPT(F) dual conduit entry
(switch rating C only)
L100
10 feet long cable assembly (switch rating A only)
L200
20 feet long cable assembly (switch rating A only)
 
Kit # 62169-19 3/16" Plastic barb fitting
(sensor 3 only)


Back to top
United Electric Controls Products
 
 

United,Electric,Controls
5320 BRADCO BLVD
MISSISSAUGA ON L4W 1G7
Tel: 905 625 5082
Fax: 905 625 5709

One Series

Copyright Owner:
Process Controls and Instrumentation
102 Wellington St E
Alliston ON L9R 1G7
Tel: (705) 435-9112 Fax: (705) 435-5277
email: webmaster@process-controls.com