LC9_-1001 |
 |
|
|
|
|
|
|
Application |
| The isolation controller has built-in intrinsic safety barriers and is CSA approved for use with associated apparatus. The controller is offered in three versions with 1 or 2 relays and 1-3 sensor inputs. The LC90 provides a high or low level switch with a single sensor input. The LC91 provides latched automatic fill or empty control with two sensor inputs. The LC92 provides latched automatic fill or empty control and an independent high or low level switch with three sensor inputs. |
|
|
|
Specifications |
| Supply voltage: |
120/240 VAC @ 50-60 Hz. |
| Consumption: |
5 watts max. |
| Sensor input: |
LC90: (1) two-wire level switch
LC91: (2) two-wire level switches
LC92: (3) two-wire level switches |
| Sensor supply: |
13.5 VDC @ 27 mA |
| Contact type: LC90: |
(1) SPDT relay
LC91: (1) SPDT relay, latching
LC92: (2) SPDT relays, (one latching) |
| Contact rating: |
250 VAC @ 10A |
| Contact latch: |
Selectable ON/OFF |
| Contact delay: |
0-60 seconds |
| LED Indication: |
Sensor, power and relay status |
| Electronics temp.: |
F: -40° to 158°
C: -40° to 70° |
| Enclosure type: |
35 mm DIN rail |
| Encl. material: |
PP, UL94VO |
| Classification: |
Associated apparatus |
| Approvals: |
CSA: Class I, Groups A, B, C & D;
Class II, Groups E, F and G;
Class III |
| Parameters: |
CSA: Voc = 17.47 VDC; Isc = 0.4597A;
Ca = 0.494 µF; La = 0.119 mH |
| Certificate: |
CSA: LR 79326 |
| CE compliance: |
EN 50082-2 immunity
EN 55011 emission
EN 61010-1 safety |
|