LH10-13_1 |
 |
|
|
| Patent Pending |
|
|
|
Application |
| The horizontal buoyancy level switch mounts through the tank’s side wall and is an excellent choice for a broad range of clean, non-coating or scaling type liquids. Media examples include sulfuric acid, process water and pure liquid solutions.
The reed output provides a reliable switch interface with remote devices such as a PLC, SCADA or alarm. The general purpose sensor features a PP submersible probe and cable, and is designed for fast installation. |
|
|
|
Specifications |
|
Orientation:
|
± 20° horizontal |
|
Accuracy:
|
± 2 mm in water |
|
Repeatability:
|
± 1 mm in water |
|
Specific gravity:
|
0.8 minimum |
|
Contact type:
|
(1) SPDT reed |
|
Contact rating:
|
120 VAC/VDC @ 15 VA
(CE: 30 Vrms and 42.2 Vpeak or 60 VDC) |
|
Process temp.:
|
F: -40° to 194°
C: -40° to 90° |
|
Pressure:
|
25 psi (2 bar) @ 25° C.,
derated @ 1.667 psi (0.113 bar)
per °C. above 25° C. |
|
Sensor rating:
|
NEMA 6X (IP68) |
|
Sensor material:
|
PP |
|
Cable jacket mat.:
|
PP |
|
Cable type:
|
3-conductor, #22 AWG (shielded) |
|
Cable length:
|
Standard: 10' (3m)
Special order: 25'
(7.6m) or 50' (15.2m) |
|
Process mount:
|
3/4" NPT (3/4" G / Rp) |
|
Mount. gasket:
|
Viton® (G version only) |
|
Classification:
|
General purpose |
|
CE compliance:
|
EN 50082-2 immunity
EN 55011 emission
EN 61010-1 safety |
|
|
Click here to download above specifications in a PDF file format. |
|
|
|
|
|
Technology |
|
BUOYANCY |
|
General purpose |
Yes |
|
Foam |
Yes |
|
Bubbles |
Yes |
|
Conductive |
Yes |
|
Non-conductive |
Yes |
|
Clean |
Yes |
|
Turbulent |
Yes |
|
Non-coating |
Yes |
|
Metallic tank |
Yes |
|
Non-metallic tank |
Yes |
|
Reed |
Yes |
|
PP sensor |
Yes |
|
PVDF sensor |
No |
|
Intrinsically safe |
No |
|
Dirty |
No |
|
Relay |
No |
|
FET |
No |
|
Light coating |
No |
|
Medium coating |
No |
|
Heavy coating |
No |
|
|
|