LV10-_2_1 |
 |
|
|
|
|
|
|
Application |
| The vertical float level switch is an excellent choice for small tank applications with clean, non-coating or scaling type liquids. Media examples include process water, chemical and acid solutions.
The reed output provides a reliable switch interface with remote devices such as a PLC, SCADA or alarm. The general purpose sensor features a PP or PVDF submersible probe and cable, and is designed for vertical installation inside the tank.
|
|
|
|
Specifications |
| Orientation: |
± 20° vertical |
| Accuracy: |
± 2 mm in water |
| Repeatability: |
± 1 mm in water |
| Specific gravity: |
0.8 minimum |
| Contact type: |
(1) SPDT reed |
| Contact rating: |
120 VAC/VDC @ 50 VA
(CE: 30 Vrms and 42.2 Vpeak or 60 VDC) |
| Process temp.: |
F: -40° to 194°
C: -40° to 90° |
| Pressure: |
25 psi (2 bar) @ 25° C.,
derated @ 1.667 psi (0.113 bar)
per °C. above 25° C. |
| Sensor rating: |
NEMA 6X (IP68) |
| Sensor material: |
12_1: PP
52_1: PVDF Kynar® |
| Cable jacket mat.: |
12_1: PP
52_1: PFA Teflon® |
| Cable type: |
2-conductor, #22 AWG (shielded) |
| Cable length: |
Standard: 10' (3m)
Special order: 25' (7.6m) or 50' (15.2m) |
| Process mount: |
3/4" NPT (3/4" Rp) |
| Classification: |
General purpose |
| CE compliance: |
EN 50082-2 immunity
EN 55011 emission
EN 61010-1 safety |
|
|
Click here to download above specifications in a PDF file format. |
|
|
|
|
|
Technology |
|
FLOAT |
|
General purpose |
Yes |
|
Foam |
Yes |
|
Bubbles |
Yes |
|
Conductive |
Yes |
|
Non-conductive |
Yes |
|
Clean |
Yes |
|
Non-coating |
Yes |
|
Metallic tank |
Yes |
|
Non-metallic tank |
Yes |
|
Reed |
Yes |
|
PP Sensor |
Option |
|
PVDF sensor |
Option |
|
Intrinsically safe |
No |
|
Dirty |
No |
|
Relay |
No |
|
FET |
No |
|
Turbulent |
No |
|
Light coating |
No |
|
Medium coating |
No |
|
Heavy coating |
No |
|
|
|