1/4
DIN Temperature Controllers
Heat / Cool Controller
Features:
• Automatic
tuning of PID parameters
• Selectable
input, heating and/or cooling outputs, degrees C or F
• 2 optional alarms, large displays 5/8" and 1 /2"
• Sealed mylar front panel, external lockout
• All control paramaters adjustable from front panel
• Automatic/manual mode operation 2" in panel depth
The 1/4 DIN Temperature Controllers can
easily be configured to provide precise control. The advanced Smarter
Logic "Fuzzy" allows processes to be controlled better than ever before,
with virtually no initial overshoot or temperature variations. As the
control detects a process disturbance the fuzzy logic continuous decision
making function quickly returns the process value to the setpoint. The
large dual displays allow the set point and process value to be visible
at all times. In addition self-diagnostic capabilities, sensor linearization
and cold junction compensation are all performed by the powerful, single
chip microprocessor. The 2" in panel depth is the shortest of any similar
function control available.
Specifications:
INPUT
Thermocouple. . . . . . .Type J,K,T,E,B,R,S,N. (selectable)
RTD. . . . . . . . . . .PT 100 ohm(DIN or JIS)
Linear. . . . . . . . . .-10-60mV Configurable input other voltage or current.
Display. . . . . . . . . in temperature or engineering units
OUTPUTS. . . . . . . . . Single output with 2 optional independant alarms
Heating and/or cooling outputs with 2 optional alarms
Relay. . . . . . . . . . SPST relay rated 3A, 240V maximum resistive load
Pulsed Voltage. . . . . .32VDC, 20mA maximum ohms
Current. . . . . . . . . 4-20mA, 0-20mA maximum load 500 ohms
Voltage. . . . . . . . . 0-10V minimum load 500K ohms
Alarms. . . . . . . . . .8 selectable modes each alarm
SPST relay(s) rated 2A, 240V maximum resistive load.
CONTROL FEATURES
Temp Range. . . . . . . . . Selectable Set Point: -1999-3182F/-1128-1750C
Alarm Set Point. . . . . . .Full Range Adjustable
Control Modes. . . . . . . .Controls can be configured as On/Off Proportional(P)
Proportional with manual reset
Proportional/Integral(PI) Proportional Derivative(PD)
Proportional/Integral/Derivative(PID)
Heating and Cooling Proportional Band:O-100% of span
Integral(Reset). . . . . . .0-3600 seconds
Derivative(Rate). . . . . . 0-1000 seconds
Anti-Reset Wind-up. . . . . Inhibits integral action outside of proportional band.
Cooling. . . . . . . . . . .Adjustable deadband from -10 to + 10o/o of cooling proportional band
Manual Mode. . . . . . . . .Configurable as open loop control should sensor no longer function
Cycle Time. . . . . . . . . 0-120 seconds
Sensor Break Protection. . .Configurable status of control and alarms
Control Action. . . . . . . Selectable-Direct action for cooling Reverse action for heating
INDICATION
Display. . . . . . . . . . .4 digit red 5/8" LED Process Value Display.
Green 1.2" LED Set Value display
Selectable decimal placement for normal or high resolution display
Example. . . . . . . . . . .0000, 000.0, 00.00 or 0.000
F/C. . . . . . . . . . . . .Selectable with 2 LED indicators
Sample Rate. . . . . . . . .250 milliseconds
POWER Supply. . . . . . . . 90-26OVAC, 50/60Hz C;onsumption: less than 5VA
Data Retention. . . . . . . 1 Oyears(EEPROM)
Control Stability. . . . . .+ - 0.15% of full scale
Accuracy. . . . . . . . . . -0.25% of range: + -1 c or 0.5C in high resolution
Cold Junction Compensation. 0.1 % ambient
External Resistance. . . . .100 ohms maximum
Common Mode Rejection. . . .120dB
Normal Mode Rejection. . . .60dB
Input Impedance. . . . . . .10M ohms
Operating Temperature. . . .14-122F-10-50C
Humidity. . . . . . . . . . 0-90% RH(non-condensing)
lnsulation. . . . . . . . . 20M ohm minimum (5OOVDC)
Breakdown. . . . . . . . . .2OOVAC,5O/60Hz 1 minute
Vibration. . . . . . . . . .10-55Hz amplitude 1 mm
Shock. . . . . . . . . . . .200m/c(20g)

|