EdgeTech DewTrak II Dew Point & Humidity Transmitter

The EdgeTech DewTrak II dew point and humidity transmitter is an optical chilled mirror hygrometer designed to continuously measure the moisture content in gases. Multiple mount options for this EdgeTech transmitter include wall, duct, pipe or remote mounting. You can also choose between a plastic (IP65) or an aluminum enclosure.

The EdgeTech DewTrak II, powered by 24 VDC, uses the chilled mirror dew point temperature condensation principle to determine the water vapor concentration in gas mixtures, and a platinum resistance thermometer to accurately measure that temperature. With an accuracy of ±0.2°C for dew point and temperature, the EdgeTech DewTrak II dew point and humidity transmitter also offers a ±0.05°C repeatability and negligible hysteresis.

Two analog outputs are available, 4-20 mA and 0-5 VDC to 0-10 VDC (selectable), on the EdgeTech DewTrak II. Other features include RS232, bi-directional and serial outputs, a static flow rate to 3,000 linear ft/min, and a response of 1°C/sec not including settling time.

Features

•Manufactured by EdgeTech
•Range:
    - Dew Point (Standard) -40°C to 60°C (-40°F to 140°F)
    - Air Temperature (Optional) -40°C to 60°C (-40°F to 140°F)
    - RH (Optional) 1% to 95%
•Accuracy: ± 0.2°C (for both Dew Point and Temperature)
•Hysteresis: Negligible
•Repeatability: ±0.05°C
•Response: 1°C/sec (not including settling time)
•Flow Rate: Static to 3,000 linear ft/min
•Analog Outputs: 2 analog ouputs (4-20mA / 0-5 Vdc to 0-10Vdc selectable)
    - Load: 4 to 20mA: 0 to 250 ohms
    - 0 to 5/10 Vdc: 1 K ohm or higher
•Relay Outputs: 2 programmable alarm relays
    - K1: Clean mirror / Alarm 1
    - K2: Servolock / Alarm 2
    - Contact Rating: Normally Open (NO) 3A at 25Vac, 0r 30Vdc
•Remote Cable Configuration:
    - Dew Point: 10 ft. standard, 50 ft. maximum
    - Air Temperature (Optional): 10 ft. standard, 50 ft. maximum
•For Dew Point: 2 stages of cooling (TEC) with a depression of 60°C