| Technical
data |
| Configurations
|
F22H-65:
wall mount or remote probe, 2-wire, loop powered
F22H-31: duct mount, 2-wire, loop powered
FH-65: wall mount or remote probe, 3-wire
FH-31: duct mount, 3-wire |
| Probe
|
HygroClip
S plug-in probe (included with transmitter) |
| Humidity
sensor |
ROTRONIC
Hygromer® C94 (capacitive) |
| Temperature
sensor |
RTD
Pt100 Ohm, 1/3 DIN |
| Sensor
protection |
Wire
mesh filter (standard) / foam filter (optional) |
| Probe
operating/measuring range |
0...100%RH
-40...85°C / -40...185°F |
| Transmitter
operating limits |
0...100%RH
and -5...60°C (23...140°F) |
| Standard
measuring ranges |
0...100%RH
0...100°F, 0...200°F, 0...50°C, -30...70°C - other ranges on
request |
| Accuracy
at 23°C / 73°F |
<±1.5%RH
and ±0.3°C / 0.5°F - special calibration on request |
| Repeatability
|
better
than 0.5%RH and 0.1°C/°F |
| Output
signals |
4...20mA,
0...5V (3-wire only) |
| Supply
voltage |
2-wire,
loop powered: 8VDC + 0.02 x load, 35VDC max.
3-wire: 24VAC or 10 ...35VDC (15VDC min. for 4-20mA)
|
| Materials
|
Enclosure:
ABS, HygroClip S: Polycarbonate |
| Case
protection grade |
IP65
/ NEMA 4 |
| Weight
|
300
g / 0.7 lb |
|
|