  Manufacturer
 Voltage Monitor and Data Logger Dickson D135
 Product  D135
 Description  Voltage Monitor and Data Logger
Image 
 Features  Ensure that your equipment and critical processes are not being adversely affected by poor power supply. The D135 Powerwatch monitor and data logger is the easiest way to record essential voltage disturbance information from any 120 volt power receptacle. Just setup your pre-determined disturbance threshold values or use the industry standard default values and plug it in. No wiring or dangerous connections required. Monitor: Surges, Dropouts, Outages and Frequency Variations.
  • Optical Alarm Indicates Logging of Events
  • Hot-Neutral; Neutral Ground Monitoring
  • User-selectable Thresholds
  • 4000 Sample Points
  • Monitors as soon as it is plugged in
  • Access data at remote locations by modem
  • Easy to use software displays real-time, graphical and statistical data
  • 30 Day Money Back Guarantee
 Notes  A160 Software required with purchase of Powerwatch Monitor. Click on the Accessories button above and select Software for pricing.
 Specifications  Ambient Operating Conditions: -40 to +158°F; 0 to 95% RH
Sample Points: 4000
Alarm: Optical; Red LED
Fuse: 1/16A fast-blow (non-replaceable)
Certifications: CSA; NRTL/C; UL1244
Battery: 3.6V Lithium; 10-years average life
Dimensions: 3.35" x 2.65" x 1.35"
Surge, Sag & Outage:
    Range: H/N: 0 to 200V rms; N/G: 3 to 200V rms Accuracy: H/N: ±1Vrms + resolution; N/G: ±1Vrms + resolution Resolution: H/N: 1V rms; N/G: 1V rms

Impulse:
    Range: H/N: 100 to 2500V peak; N/G: 50 to 2500V peak Accuracy: H/N: ±10% or reading + resolution; N/G: ±10% or reading + resolution Resolution: H/N: 10V; N/G: 10V Width Detection: H/N: 1µsec minimum; N/G: 1µsec minimum

Phase Angle
    Accuracy: H/N: ±1° (20 to 180°, 200 to 360°); N/G ±1° (20 to 180°, 200 to 360°) Resolution: H/N: 1° N/G: 1°

Time Events (<1 sec):
    Accuracy: H/N: ±0.5 cycle; N/G: ±1 cycle Resolution: H/N: 0.5 cycle; N/G: 1 cycle

Frequency:
    Range: 45 to 65 HZ Accuracy: ±0.1Hz (3 cycles minimum) Resolution: 0.1Hz

Time-stamp
    Accuracy: ±2 sec./day + resolution Resolution: 8 seconds