Universal,Input,Chart,Recorder,Dickson

Universal Input Chart Recorder


  Process Controls Home
  Products
  General Information
  Manufacturer
  Universal Input Chart Recorder
 Product  ESX
 Description  Universal Input Recorder - 8" Chart
 Image 
 Features  The Dickson ESX signal recorder offers the flexibility of a standardized input recorder that can be used for a wide variety of applications. The microprocessor-based instrument offers high accuracy, flexibility and many other features normally offered only on higher priced recorders.
  • Remote sensing capability with powered voltage or current transmitters
  • High/Low Alarms feature and display of Min/Max readings (no controller/relay functions)
  • User selectable output ranges and recording times
  • Two screw terminals on back of the instrument allows easy connection of the input transmitter
  • Locking control keypad & door
  • User calibration
  • User selectable input/output ranges and recording times
  • AC Power with battery back up
  • Keyhole slots for wall mounting
  • User selectable decimal point placement to create desired output range on the display
  • Large digital display
  • Large 8" diameter chart
  • 30 Day Money Back Guarantee
 Notes  To order additional charts, pens, extended warranty or carrying case, click on the Accessories button above and select from the available options.
Available Charts
C409: 0 to +100, 31 day
C410: 0 to +100, 24 hr
C412: 0 to +100, 7 day
C420: 0 to +10, 24 hr
C498: 0 to +10, 7 day
C457: 0 to +14, 24 hr
C453: 0 to +14, 7 day
C456: 0 to +200, 24 hr
C436: 0 to +200, 7 day
C424: 0 to +30, 24 hr
C463: 0 to +30, 7 day
 Specifications  Accuracy: .3% full scale ±1 digit (recorder only)
Ambient Operating Conditions: (recorder) +32 to +120°F (0 to +50°C), 0 to 90% RH (non-condensing)
Power Supply: 120V AC Adapter, (other adapters available for international markets) use four "D" batteries for battery back up (not included)
Alarms: Audio (90 decibel)/Visual and over current high and low alarms (warning mechanism, no controller/relay functions).
Average Battery Life: 1-day recording mode = 2 months, 7-day = 3 months, 31-day = 4 months
Average Response Time: 20 seconds full scale (depending on transmitter) Note: The ESX internally averages readings together. In battery mode the update rate is slowed to conserve power & since the unit takes 1 new reading per update the response is also slowed.
Calibration: NIST Traceable to our RFL electrical signal generator
Calibration Adjustment: User calibration (calibration best accomplished when used with transmitter that will be used)
Calibration Kit: Not available for this model
Chart Size: 8" diameter (20.3cm)
Dimensions: 10.5" x 13.2" x 2.8" (26.7cm x 33.5cm x 7.1cm)
Display Resolution: 0.001, 0.01, 0.1, or 1 depending on range selected
Input Ranges: (User selectable) 0-20mA, 4-20mA, 0-5 Vdc, 1-5 Vdc
Maximum Input Voltage: 5 volts (instrument records direct current-dc)
Mounting: Free standing or wall mountable
Output Ranges: (user selectable, including decimal point selectability) 0 to +10, 0 to +200, 0 to +45, -150 to +250 0 to +100, 0 to +2000, 0 to +500, -20 to +50 0 to +1000, 0 to +250, 0 to +60, -20 to +120 0 to +14, 0 to +30, +40 to +110, -30 to +50 0 to +150, 0 to +300, -.10 to +.10, -50 to +50
Recording Time: User selectable: 1, 7 and 31 day
Transmitter Capability: Any self powered voltage or current transmitter with specified recorder input range. (Transmitter range & recorder output range should be the same)
Impedance: 10 ohms Caution: To connect a transmitter to the recorder. Locate the terminal block on the back of the recorder. Connect the positive wire of transmitter to positive terminal (left) of recorder and the negative wire of transmitter to negative terminal (right) of recorder. Tighten screws in terminal block to hold in transmitter wires. It is important that the voltage/milliamp switch on recorder and dip switch #3 corresponds to the transmitter being used.
Warranty: 1-year
Weight: 3.5 lbs. without batteries (1.5 kg), 5 lbs. with batteries (2.2kg)
Includes: Pen, Box of 60 (0 to +100/7 day) Charts, AC adapter and Instructions
 Manuals  ESx.manual.pdf

Universal Input Chart Recorder


Site Designed By Panther Marketing & Design