| Product |
FT121 |
| Description |
Flat Panel LCD Recorder with K-Thermocouple Temperature Probe (°F/°C Switchable) |
| Image |
|
| Features |
Dickson's newest Flat Panel LCD Recorder, FT121, lets you view detailed temperature data on its large screen and allows for optional PC downloads. Its large 4.5" x 2.5" display shows you current temperature readings and displays a graph of data ranging from 1 hour to 32 days. The remote K-Thermocouple probe allows you to monitor temperatures from -200 to +2000°F/C, while an internal sensor records ambient temperature conditions. No paper charts or running back to your PC to see data. This recorder shows you everything at the push of a button.
Ideal for:
- Monitoring HVAC/R Systems
- Checking Refrigerator, Freezer and Cooler Conditions
- Monitoring Ovens, Autoclaves and Baths
- Tracking Critical Processes
- Gathering Data from Hard to Reach Places
- 30 Day Money Back Guarantee
|
| Notes |
Additional Flat Panel LCD Logger Models Include:
FH121 Self Contained Temperature and Humidity Flat Panel LCD Logger - perfect for monitoring building automation systems.
FH125 Remote Probe Temperature and Humidity Flat Panel LCD Logger - perfect for chambers, incubators and hard to reach places.
A015 Software and Download Cable required to download logged data to PC.
To order calibrations, software, K-Thermocouple probes or the locking wall mount case, click on the Accessories button above and select from the available options. |
| Specifications |
Temperature Ranges (User Selectable):
FH121: 0 to +100°F (0 to +50°C);
FH125 (Remote Probe Model): 0 to +100°F, -40 to +185°F, 0 to +120°F, -20 to +40°C, -40 to +85°C, -20 to +50°C;
FT121 (Remote Probe K-TC Model): External Temperature Ranges (User Selectable): 0 to +100°F/C; 0 to +250°F/C; 0 to +500°F/C; 0 to +1000°F/C; 0 to +2000°F/C; -50 to +50°F/C; -100 to +100°F/C; -200 to +200°F/C (internal channel) 0 to 120°F, -17.8 to 48.9°C
Temperature Accuracy: ±1.8°F (recorder only)
Humidity Range: 0 to 95% RH
Humidity Accuracy: ±2% RH at 73°F
Remote Probe: K-Thermocouple; 4' Bead Wire; Mini Connector; +500°F (see accessories for optional probes)
Sample Points: 15,872 per channel
Recording Times: User Selectable: 64 minutes, 8 hours, 24 hours, 8 days, 16 days or 32 days
Sample Rate: Sampling Rates for each Recording Time: 64 minutes samples every 20 seconds, 8 hours and 24 hours samples every 30 seconds, 8 days and 16 days samples every 60 seconds, 32 days samples every 150 seconds
Display: LCD; 240 x 128 pixels; Graphical Display
Recording Times: User Selectable: 64 minutes, 8 hours, 24 hours, 8 days, 16 days or 32 days
Resolution: 0.1°F
Power: 120V AC with 9V battery backup
Dimensions: 7" x 5" x 2"
Weight: 1.2 lb.
Optional NIST traceable certificate of calibration available |