Foundation,Fieldbus,Pressure,Transmitter,Series,SMAR,LD302

Foundation Fieldbus Pressure Transmitter
Series SMAR LD302


  Process Controls Home
  Products
  General Information
  Manufacturer
 Foundation Fieldbus Pressure Transmitter Series SMAR LD302

LD302
Foundation Fieldbus Pressure Transmitter Series

The LD302 is a transmitter based on the field proven capacitive sensor that measures absolute, gage and differential pressure using digital sensing. As an intelligent device, it can perform control functions, flow totalization and drive final control elements through the bus. The LD302 can also be configured as a FIELDBUS master station. Configuration can be accomplished through the Syscon software.

The LD302H is a special feature of the LD302D. It is built to measure differential pressures in processes with high static pressure.

The LD302S series are transmitters, using sanitary flange on the high side. Their technical specifications are the same contained in the LD302 catalog. The specification for accuracy, drift, and temperature effect are the same as that of the LD302L.

The LD302S are transmitters for food and other application where sanitary connections are required. They are used where clear-in-place applications are needed. The process connection can be threaded or clamped (Tri-Clamp), to allow a quick and easy connection and disconnection from the process. Wetted surface finish is 3Aa as standard. These series meets 3A recommendation so that the seal surface is free of crevices where food or bacteria can be collected and the finish is extremely smooth. 3A is the most widely accepted sanitary standard in the food, drug, and beverage industry.

The LD302T is a hydrostatic pressure transmitter. It measures static pressure with high accuracy provided by its conical-like shape.

Some Characteristics:
Communication
FOUNDATION Fieldbus on 31.25 kbit/s voltage
mode according to IEC 61158-2
Range
0 to 40 MPa (5800 psi)
Rangeability
Accepts calibration from URL to URL/40
Accuracy
± 0.075% of calibrated span
Power Supply
Bus powered: 9-32 Vdc
Power Consumption
Quiescent 12 mA
Function Blocks
Up to 20 Dynamically Instantiable Function Blocks.
The Function Blocks available allow simple and complex control strategies to be placed inside the field device, making the field device an integral part of the control system. In order to fully benefit from the Function Blocks in the device a True Foundation Fieldbus system is recommended.
Indicator
Optional 41/2-digit numerical and 5-character alphanumerical LCD indicator
Ambient Temperature Limits
-40 to 85 ºC (-40 to 185 ºF)
Process Temperature Limits
-40 to 100 ºC (-40 to 212 ºF) (Silicone Oil)
0 to 85 ºC (-32 to 185 ºF) (Fluorolube Oil)
-40 to 150 ºC (-40 to 302 ºF) for LD302L
-25 to 85 ºC (-13 to 185 ºF) (Viton O-Rings)
Ambient Humidity Limits
0 to 100% RH
Wetted Parts
Plated carbon steel, 316L SST, Hastelloy C276, Monel or Tantalum
Nonwetted Parts
Injected aluminum with polyester painting or 316 SST
Hazardous Area Certification
Explosion proof, weather proof and intrinsically safe
Weight
3.15 kg (7 lb): all models, except level transmitters: 5.85-9 kg (13-20 lb)

Foundation Fieldbus Pressure
Transmitter Series SMAR LD302

Site Designed By Panther Marketing & Design