Monarch
Paperless Recorder DataChart 5000 Series
Features
Monarch
Paperless Recorder DataChart 5000 Series
Inputs
& Computation Channels
Choose
6 or 12 universal, isolated direct inputs plus computation
channels for a total of 15.
- Measurement
types: linear, square root, log linear. T/C, RTD, frequency/pulse,
calculated, conditional, dry contact and external via serial
cornrnunications port.
- 3
scaleable voltage input ranges: +/- 100mV +/- 1 Volt and
+/- 10 Volts.
- Current
Ranges: 4-20mA and 10 - 50mA with internally switched 50
ohm shunts.
- Thermocouples:
B, C, E, J, K, R, S, T, Nickel/Nickel Moly and Nicrosil-Nisil.
- RTD's:
10 ohm Cu, 100 ohm Pt 385. 100 ohm Pt 392, 200 ohm Pt 385,
200 ohm Pt 392 and 120 ohm Nickel.
- Easy
setup and versatile scaling.
Monarch
Paperless Recorder DataChart 5000 Series
Display
Brilliant
5.6 inch active matrix (TFT) color display is CCFL backlit,
and can be dimmed for optimal viewing. A rugged Touch
Screen makes set up and operation simple. Browse data
file information from RAM or disk while recording. Real Time
or historical data review. Display modes include:
- Graphic
trend - vertical or horizontal
- Bargraphs
- vertical or horizontal
- Digital
meters
- Alarm/Event
Summary
- Split
screen combinations
|
Status
windows include:
- Time/Date
- Alarms
- Disk
capacity used
- Menu
Monarch
Paperless Recorder DataChart 5000 Series
High
Accuracy Measurement
Isolated
input modules coupled with a fast 16 bit A/D converter provides
voltage measurement accuracy of +0.05%
Monarch
Paperless Recorder DataChart 5000 Series
Measurement Recording and Display Rates
- Each
channel is measured eight times per second (125mS).
- Recording
rates are independently selectable in 1 second intervals
for each channel and range between 8 per second to 1 every
10 minutes
- Data
display update rates are selectable from 0.25 to 60 seconds.
- Virtual
chart speed is selectable from 0.5in to 600in/hr (10mm to
15000mm/hr).
Monarch
Paperless Recorder DataChart 5000 Series
High
Quality Modular Design
- The
modular design of the DC-5000 allows options to be added
in the field quickly and easily.
- Data-Chart
Paperless Recorders and Accessories have a full two year
comprehensive warranty.
Monarch
Paperless Recorder DataChart 5000 Series
Programming Features
·
Menu selectable via intuitive Touch Screen
· Selectable signal input type and range.
· Application dependent scale ranging (up to + 5 digits
or Exponential notation).
· Selectable signal filtering.
· Engineering units - up to 5 character alphanumeric.
· Point tag - up to 10 characters (6 displayed).
· Program for normal or alarm/event triggered recording mode.
· User selectable multilevel passcode protection.
Monarch
Paperless Recorder DataChart 5000 Series
Computation Channels
- Math
functions include +, -, x, +, square root, totalization,
moving average, timed average, delta, gated timer, peak.
valley, logarithms, algebraic equations, conditional statements
and 12 programmable constants.
- Minimum
of 9 computation channels available.
- Computation
channels can be displayed, recorded and alarmed.
Monarch
Paperless Recorder DataChart 5000 Series
Data Storage
- 3,5inch
floppy disk (1.44Mbyte capacity, IBM format)
- PCMCIA
memory card (Flash to 220 Meg).
- Internal
1Meg RAM buffer provides historical data review on site
while still recording real time information. optional expansion
to 2 Meg RAM is available.
- Search
data files by date/time or signal value.
- Transfer
data files to IBM compatible PC's via serial communications
port.
- Independent
data files for up to 12 channels, alarm/event file and configuration
files.
- Customize
file names for each recording session.
- Review
historical information while recording in real time
- Fill
to end mode with user selectable disk full alarm.
- Cyclical
storage mode.
Monarch
Paperless Recorder DataChart 5000 Series
Recorder
Control
The
following functions can be controlled via external inputs
or internal alarms
|
Function
|
External
|
Internal
|
| Record
on/off |
Yes |
Yes |
| Record
rate |
Yes |
Yes |
| Chart
Speed |
Yes |
Yes |
| Totalizer
Reset |
Yes |
Yes |
| Event
message |
Yes |
No |
| Alarm
Ack/Reset |
Yes |
No |
| Scale
Set |
Yes |
No |
Monarch
Paperless Recorder DataChart 5000 Series
Alarms
- 5
alarm set points per channel (60 total) include: high, low,
rate of change. true, false and abnormal signal conditions.
- 3
or 6 alarm contact outputs.
- Latching,
non-latching, failsafe, reflash and acknowledge.
Monarch
Paperless Recorder DataChart 5000 Series
Communications
· RS232 bi-directional with modem
support.
· RS485 network
port - address up to 31 units
· Serial protocol
· MODBUS
RTU or MODBUS ASCII.
· Real time
and data file transfer to IBM compatible PC's.
· Remote configuration.
· User selectable baud rates from 300 to
19,200bps.