Technical Data | Ordering Data | Downloads | Back
Our Solid Core Current Transducer converts a monitored AC current to a proportional 4-20 mA output.
Applications:They are used to monitor pumps, motors, conveyors, machine tools, and any electrical load where an analogue representation is required over a range of currents. All models are UL, ULC and CE listed.
Description:The Sentry 200 Solid Core Current Transducer comprises a current transformer, power circuit, precision rectifier, high-gain servo amplifier, and span and zero adjustments. Each sensor has three user selectable ranges. The two wire loop powered 4-20 mA output is available on two 6-32 screw terminals.
Technical Data| Size: | Units are 2.18" H x 3.53" W x 0.93" D with an integral mounting base 3.5" long and mounting centres of 3". The through hole is 0.75" diameter. |
| Operating temperature: | -20°C to +50°C. |
| Case: | ABS (Meets UL flammability rating 94V-0) |
| Accuracy: | ± 0.5% of full scale. |
| Repeatability: | ± 0.1% full scale. |
| Frequency: | Flat from 20-100 Hz. |
| Response Time: | 300 msec (90%) |
| Ripple: | Less than 10 millivolts. |
| Supply: | 12 to 40 VDC |
| Protection: | Reverse polarity, high current |
Electrical Specifications:
| Model | Range | Jumper | Max Current |
| Sentry 200-1 | 0 to 10A | None | 80A 110A 175A |
| 0 to 20A | Mid | ||
| 0 to 50A | High | ||
| Sentry 200-2 | 0 to 100A | None | 200A 300A 400A |
| 0 to 150A | Mid | ||
| 0 to 200A | High |
| Sentry 200-1 | for ranges of 0 to 10, 0 to 20, and 0 to 50 amps full scale. |
| Sentry 200-2 | for ranges of 0 to 100, 0 to 150, and 0 to 200 amps full scale. |
Output is linear with input.
DownloadsAll files are in PDF format and may be read with Adobe Acrobat Reader
Technical Data | Ordering
Data | Downloads | Back | Top