Pressure,Transmitters,Stainless,Steel

Pressure Transmitters - Stainless Steel

Technical Data | Installation & Operation | Ordering Data | Downloads | Back

Pressure Transmitters - Stainless Steel
Model 4340

Pressure Transmitters determine the pressures in liquids and gases and convert these pressures to an electrical signal. The 4340 features compact construction, an integral amplifier, large output signal and extensive medium compatablility. The design provides a 1/2% accurate, economical transmitter that can operate accurately over a wide temperature range with corrosion resistance.

Pressure Transmitters - Stainless Steel - Technical Data

Wetted parts / Case: Stainless steel 316L & 446/ s/s 304 & polycarbonate
Ambient/Medium temperature: -40...+85°C
Pressure Connection: 1/4" NPT
Supply Voltage: 12...30VDC (incl. peaks), 20 mA max. loading
Output: 2-wire 4 to 20 mA, max load = U-12V/0.02A
Accuracy: 1%
Errors: load < 0.15%, ambient temperature 0.05%/°C
Hysteresis: 0.2% max (linear characteristic)
Overload limit: 200% full scale
Enclosure: IP65 (NEMA 4)
Response time: 10 msec
Operating position: unrestricted

Pressure Transmitters - Stainless Steel - Installation & Operation

Operation

The ceramic coated steel diaphragm sensing element deflects under pressure. This deflection is transmitted to a thick-film resistor network mounted on the ceramic layer which causes the connected pair of opposite resistances to either expand or contract. This produces a positive or negative resistance change proportional to the pressure. A constant voltage supply to the bridge followed by a differential amplifier converts the signal to a magnified proportional voltage output.

This is added to a temperature dependent reference voltage and electronically compensated for temperature drift. The signal is finally converted via a voltage controlled current source to a standard 4-20 mA signal.

Caution

Always use a wrench on the stainless steel fitting to tighten the transmitter into the process. Using the body of the transmitter to tighten it by hand can cause permanent damage.

Installation
  1. To open plug remove screw 1.
  2. Insert a screw driver through the cable opening and lever the terminal block 3 out of the shell 2.
  3. Thread the connection cable through the cable tie down screw, the metal washer, the rubber washer and the cable opening.
  4. Connect the positive lead to terminal 1 & the negative lead to terminal 2.
  5. The terminal block can be rotated inside the shell as desired to allow the cable to exit on the most convenient side.
  6. Re-assemble the connector and screw to the body of the pressure transmitter.

Pressure Transmitters - Stainless Steel - Ordering Data

Range Order #
-30" Hg ... 15psi 4341-3015
0 ... 30psi 4341-30
0 ... 60psi 4341-60
0 ... 100psi 4341-100
0 ... 160psi 4341-160
0 ... 250psi 4341-250
0 ... 500psi 4341-500

Pressure Transmitters - Stainless Steel - Downloads

Data Sheet

Installation & Operation

All files are in PDF format and may be read with Adobe Acrobat Reader

Technical Data | Installation & Operation | Ordering Data | Downloads | Back | Top of page



Pressure Transmitters - Stainless Steel