Liquid
Level Controller
|
•
Automatic control of liquid level
• Solid-state sensing circuit
• Adjustable sensitivity
|
Liquid Level Controller
The Model 409 Liquid Level Controller
is a compact, socket-mount device for level control of conductive liquids.
The Internal relay is energized when operating power is applied. When
the liquid level reaches the probe, the relay de-energizes. When the
level drops below the probe, the relay will reset.
A fixed, two-second time delay prevents oscillation due to wave action.
Probe cables may be shielded or unshielded. If the liquid container
is made of a non-conductive material, a common electrode is required.
Other features include an LED indicator to show the output relay status
and an adjustable sensitivity setting. Options such as a normally de-energized
relay, longer time delays, etc., are available on request. Requires
a standard 8-pin octal socket. (socket number 51X00120-01)
Liquid Level Controller
Specifications:
Model 409
Operating voltages:
24 VAC: 20-30 VAC, 50-400 Hz
120
VAC: 90-140 VAC, 50-400 Hz 230
VAC: 200-250 VAC, 50-400 Hz
Power consumption: 2.5W
Transient
Protection: 2500VRMS for 10msec
Probe Voltage: 2 VAC (logic
level)
Probe Current: 5mA
maximum
Sensitivity Adjust: 1K ohms-100K
ohms
Contacts: SPDT
Contact Rating: 10A @ 240 VAC
resistive
Expected Relay Life:
Mech: 10,000,000 operations
Elec: 100,000 at rated load
Response Time: 2 seconds
Reset Time: <1 second
Reset Method: Automatic
Time Delay Accuracy: ±5%
Operating Temp: - 40° to 60°
C
Humidity Tolerance: 0-97% w/o
condensation
Case Material ABS: plastic
Weight: 4.5 oz. Max.
|