Process Instruments Inc., has designed its API signal conditioning products
with exclusive features which will prove invaluable during the equipment
installation and start-up phases of a project. On transmitters, Absolute
Process Instruments Inc., uses a series of LED's which we call LoopTrackers
to monitor the presence and intensity of an input or output signal.
The LoopTracker can be very helpful when checking for proper wiring
and connection integrity. Bi-color LED's are used on alarm units to
indicate relay status along with a special test button feature which
allow an installer to toggle the alarm.
The LoopTracker
LED's as a Diagnostic Tool
The API LoopTracker
LED's track the input/output signal by varying its intensity with the
process signal. As the signal increases the intensity of the LED increases
and as the signal decreases the LED's intensity also decreases. Should
a problem develop in the loop (i.e., a faulty device in the loop) causing
an incomplete path for current, the LoopTracker detects this and ceases
to illuminate. This function works on both the Input and Output loop
allowing the technician to diagnose the cause of the problem quickly
and efficiently therefore minimizing system downtime.
Functional
Test Pushbutton
On Transmitters
The Functional Test
Pushbutton on each API Transmitter will, when depressed, output a signal
independent of the input signal. This signal is fully adjustable from
0-100% of span by holding the Test Pushbutton down and adjusting the
"Test Cal." potentiometer on the unit.
This feature allows the technician to inject a Test or preset Calibration
signal into the output loop without manipulating the input signal. This
signal can be used to check loop status, downstream display operation,
downstream alarm operation, etc.
For
example, before the "Push-to-Test" button is pressed,
the signal is: 4 mA input - 4 mA output. With the potentiometer set
at 50% and the "Push-to-Test" button pressed, the signal is:
4 mA input - 12 mA output.
On Alarms
The Functional Test
Pushbutton on each API Alarm will, when depressed, change the current
state of the relays and Bi-Color LED's regardless of the input signal
level. When released the relay will return to its normal operating state.
An added feature of the Test Pushbutton is when depressed in the Latching
Mode it allows manual reset of the latched alarm, provided an alarm
condition no longer exists for that setpoint.
The Functional
Test Pushbutton allows the technician to test the function of the relays
as well as the operation of the device the relays are controlling. For
example: an API 1000 G is used as a high level alarm to prevent the
overflow of a wastewater tank. The relays are wired to a pump which,
when a high level is detected, turns on and pumps the wastewater to
an "overflow" tank. Since overflowing the tank to test the
pump is impractical, the technician simply has to depress the Test Pushbutton
and check the operation of the pump.
The
Bi-Color LED's on API Alarms
The API Alarm family provides alarm status indication via a Bi-Color
LED for each setpoint. The Bi-Color LED indicates Green for a Non-Alarm
condition and Red for an Alarm condition whether or not the unit is
configured for "Normal" (Fail-Safe) or "Reverse" (Non-Fail-Safe) acting.
See following text for contact position and coil state in each of these
conditions.
"Normal" (Fail-Safe)
Relay Operation
In the "Normal" (Fail-Safe)
mode of operation the LED will indicate Green for a Non-Alarm condition.
In this non-alarm condition the relay coil is energized and the
"C" and "NO" contacts are made. When the process signal crosses the
preset setpoint the LED will indicate Red for an Alarm condition. In
this Alarm condition, the coil de-energizes causing the "C" and
"NC" contacts to be made. Should the alarm lose operating power due
to a service interruption the coil will de-energize and fail to a "Safe"
or Alarm condition.
"Reverse" (Non-Fail-Safe)
Relay Operation
In the "Reverse"
(Non-Fail-Safe) mode of operation the LED will indicate Green for a
Non-Alarm condition. In this non-alarm condition the relay coil is de-energized
and the "C" and "NC" contacts are made. When the process signal crosses
the preset setpoint the LED will indicate Red for an Alarm condition.
In this Alarm condition, the coil energizes causing the "C" and
"NO" contacts to be made. Should the alarm lose operating power in the
"Reverse" mode the coil will de-energize and fail to a "Non-Safe" or
Non-Alarm condition.
Exclusive Standard Features
Listed below are exclusive features that are standard on all
API alarm trips, isolators and signal conditioners:
- Lifetime
warranty
- 2000
VRMS optical isolation
- Multiturn
setpoint & deadband controls
- Field
selectable HI/LO alarms
- Heavy-duty
7-amp relay contacts
- AC power
- True
fail-safe alarm trips
- Industry-standard
plug-in bases
- High-impact
polycarbonate cover
- Glass
epoxy PC boards
- Integral
DC power supply to drive loop power device
- Adjustable
deadbands for each setpoint on dual alarms
Remember,
at Absolute Process Instruments Inc., there's never a factory
calibration charge and there's never an expediting
fee.