Boiler Feed Pump Systems
From Albany Pump Company Ltd
|

|
|
Simplex Boiler Feed Pump System
Includes one pump and motor unit sized to handle rated boiler horsepower with a 300% safety margin. A horizontal steel holding tank is mounted above the pump with necessary openings for returns, vent and drain. A float operated make-up water valve is standard. Suitable pipe connections from the tank to the pump are provided and include a suction strainer and hand operated valve. All components are mounted on a steel base. Pump operation is controlled from the boiler.
|
|
|
Duplex Boiler Feed Pump System
Includes two pump and motor units, each sized to handle rated boiler horsepower with a 300% safety margin. Since each pump is sized to adequately handle rated boiler either pump pump can be removed for service or adjustment without interruption of system operation. A horizontal steel holding tank is mounted above the pumps with necessary openings for returns, vent and drain. A float operated make-up water valve is standard. Suitable pipe connections from the tank to the pump are provided and include a suction strainer and hand operated valve. All components are mounted on a steel base. Pump operation is controlled from the boiler.
|
|
|
Sizing a Boiler Feed Pump System
Condensate Return Pumps are sized based on 0.2 USGPM per boiler Horsepower or 3 times the actual evaporation rate. For Example: A 100 Horsepower Boiler requires a 20 USGPM pump.
|

|
Search This Site
(Search by Product Type i.e. Level or Brand Name i.e. Walchem)